Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE01-03617 ELE-Aging Inspection9/4/20039/4/20039/4/2003 12:00:00 AM PART
WSUC 9/10/2003 2:30:54 PM
ELE03-00185 ELE-Aging Inspection9/4/20039/4/20039/4/2003 12:00:00 AM PART
called they call for inspection when ready 9/10/2003 2:30:11 PM
ELE03-02472 Electrical Rough-In9/4/20039/4/20039/4/2003 12:00:00 AMAPART
u/g behind north tower
ELE03-00067 Final9/3/20039/4/20039/4/2003 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 9/3/2003 at 3:12:58 PM. Contact: ###-####. ok 9/4/2003 7:56:24 AM
ELE03-02322 Final9/3/20039/4/20039/4/2003 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 9/3/2003 at 3:51:03 PM. Contact: ###-####. 210.8(B)(3) gfci for all recepts in kit, old and new, 200.6, or 250.119 shall not ID 6 or smaller, cor. poste for school district work done without permit 9/4/2003 9:38:57 AM
ELE03-02430 Final9/3/20039/4/20039/4/2003 12:00:00 AMAFAIL
final inspection; Phone #: ###-#### Internet Inspection Request from: Andy Rose p/s is a mess contractor will set up conference needs main ahead of split bus panel address clearences for p/s and sub panel no violations to be retained called 9/4/2003 10:20:46 AM
ELE03-01840 Electrical Rough-In9/3/20039/4/20039/4/2003 12:00:00 AMAPASS
craig elec-call 1st before insp; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called left message 9/4/2003 9:53:08 AM ok 9/4/2003 11:18:05 AM
ELE02-02684 Electrical Rough-In9/3/20039/4/20039/4/2003 12:00:00 AMAPART
ernest; Phone #: ###-#### Internet Inspection Request from: Marc Lileks correction for power blinds ok 9/4/2003 8:43:41 AM
ELE03-02352 Final9/3/20039/4/20039/4/2003 12:00:00 AMPFAIL
monument sign located on west side of driveway into clinic. Thanks Robin; Phone #: ###-#### Internet Inspection Request from: Susie Seltzer ne3ed access to sign interior called sign company will schedule inspection 9/4/2003 3:53:25 PM
ELE03-02717 Final9/3/20039/4/20039/4/2003 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 9/3/2003 at 9:13:04 PM. Contact: ###-####. ok 9/4/2003 4:29:47 PM
ELE03-01882 Final9/4/20039/4/20039/4/2003 12:00:00 AMPPASS
al; Phone #: ###-#### Internet Inspection Request from: Annette Moore ok 9/4/2003 2:05:20 PM
ELE03-01881 Final9/4/20039/4/20039/4/2003 12:00:00 AMPPASS
al; Phone #: ###-#### Internet Inspection Request from: Annette Moore ok 9/4/2003 2:05:15 PM
ELE03-02730 Conference9/4/20039/4/20039/4/2003 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 9/4/2003 at 10:00:05 AM. Contact: ###-####. needs bushings for rigid nipple and chase nipple at nsign pole bell box 9/4/2003 2:59:33 PM
ELE03-02741 Rough-In Permanent Service9/4/20039/4/20039/4/2003 12:00:00 AMPPART
rick; Phone #: ###-#### Internet Inspection Request from: Darla Downs r/i for new basement bath ok needs clearence for sub panel 110.26(F)(1) there is no p/s 9/4/2003 12:58:24 PM
ELE03-02681 Final9/4/20039/4/20039/4/2003 12:00:00 AMPNH
Scheduled by a contractor via Hello! on 9/4/2003 at 11:20:19 AM. Contact: ###-####. called no access
9/4/2003 2:58:12 PM
ELE03-02755 Electrical Rough-In9/4/20039/4/20039/4/2003 12:00:00 AMPFAIL
called covered be inspection, 300.5 u/g not deep enough, needs approved jbox called
ELE03-01573 Final9/4/20039/4/20039/4/2003 12:00:00 AMPPASS
ok