Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00158 FIR-Aging Inspection9/4/20039/4/20039/4/2003 12:00:00 AM PASS
this building is still under construction 9/4/2003 7:11:15 AM
FIR03-00135 INSP-Sprinkler Rough-in9/4/20039/4/20039/4/2003 12:00:00 AMAPART
okay to cover rooms; corridor pipe not restrained to prevent upward movement; fire stopping required in corridor 9/4/2003 8:57:27 AM
FIR03-00136 INSP-Sprinkler Rough-in9/4/20039/4/20039/4/2003 12:00:00 AMAPART
okay to cover rooms; corridor pipe not restrained to prevent upward movement; fire stopping required in corridor 9/4/2003 8:57:33 AM
FIR03-00137 INSP-Sprinkler Rough-in9/4/20039/4/20039/4/2003 12:00:00 AMAPART
okay to cover rooms; corridor pipe not restrained to prevent upward movement; fire stopping required in corridor 9/4/2003 8:57:40 AM
FIR03-00138 INSP-Sprinkler Rough-in9/4/20039/4/20039/4/2003 12:00:00 AMAPART
okay to cover rooms; corridor pipe not restrained to prevent upward movement; fire stopping required in corridor 9/4/2003 8:57:49 AM
FIR03-00139 INSP-Sprinkler Rough-in9/4/20039/4/20039/4/2003 12:00:00 AMAPART
okay to cover rooms; corridor pipe not restrained to prevent upward movement; fire stopping required in corridor 9/4/2003 8:57:17 AM
MIS03-00167 FIR-Final9/3/20039/4/20039/4/2003 12:00:00 AMAFAIL
###-#### richard address 4inches; main exit keyed both sides with "Door to remain..." sign; rear exit openable from the inside without special knowledge; fire extinguisher needed 9/4/2003 8:55:52 AM
FIR03-00464 INSP-Final Inspection9/3/20039/4/20039/4/2003 12:00:00 AMACANC
received call and this will be rescheduled 9/4/2003 10:28:07 AM
BLD03-01681 FIRE-Final Inspection9/3/20039/4/20039/4/2003 12:00:00 AMAFAIL
jim; Phone #: ###-#### Internet Inspection Request from: Annette Moore one detector didn't shut down the AHU on north side 9/4/2003 4:00:50 PM
FIR03-00115 INSP-Sprinkler Rough-in/Hydro9/3/20039/4/20039/4/2003 12:00:00 AMAPART
okay to cover rooms; corridor pipe not restrained to prevent upward movement; fire stopping required in corridor 9/4/2003 8:57:56 AM
BLD03-00866 FIRE-Final Inspection9/3/20039/4/20039/4/2003 12:00:00 AMAFAIL
dirk; Phone #: ###-#### Internet Inspection Request from: Barbara Moore storage racks over 8 ft - need racking permit; need annual fire sprinkler report and access to riser room 9/4/2003 10:27:39 AM
FIR03-00476 INSP-Final Inspection9/4/20039/4/20039/4/2003 12:00:00 AMPFAIL
todd; Phone #: ###-#### Internet Inspection Request from: Annette Moore need smoke detector above fire alarm panel, manual pull station and audible alarm; need sign on riser room door - "Fire sprinkler controls"; need annual inspection report to verify Ames 2000 backflow preventor doesn't cycle open/closed; appears to need Knox box - couldn't locate 9/4/2003 1:20:05 PM
FIR03-00426 INSP-Conference9/4/20039/4/20039/4/2003 12:00:00 AMPPART
russ; Phone #: ###-#### Internet Inspection Request from: Marc Lileks met with Russ and GC about minor changes in hallway due to ceiloing changes; dry sidewall to east canopy can be eliminated if it is noncombustible 9/4/2003 3:19:49 PM