FIR03-00290
| FIR-Aging Inspection | 9/4/2003 | 9/4/2003 | 9/4/2003 12:00:00 AM | | NR |
|
|
work in progress 9/5/2003 7:22:37 AM
|
BLD01-02249
| FIRE-Conference | 9/2/2003 | 9/4/2003 | 9/4/2003 12:00:00 AM | A | CANC |
|
|
the contractors and I's schedules did not work out. He will call it in next week 9/4/2003 11:45:57 AM
|
BLD02-02471
| FIRE-Final Inspection | 9/3/2003 | 9/4/2003 | 9/4/2003 12:00:00 AM | A | FAIL |
|
|
cameron; Phone #: ###-#### Re-install the covers on the duct smoke detectors 9/4/2003 9:43:18 AM
|
BLD02-02264
| FIRE-Final Inspection | 9/3/2003 | 9/4/2003 | 9/4/2003 12:00:00 AM | A | FAIL |
|
|
Provide fire extinguishers in the generator rooms per review note #11, finish painting of the curbing for fire dept access per review note #7 and conversation, repair emergency light in room 002 and raise the existing fire hydrant so the barrel is a min. 18" above finish grade per United Water requirements 9/4/2003 11:43:48 AM
|
BLD03-01233
| FIRE-Final Inspection | 9/3/2003 | 9/4/2003 | 9/4/2003 12:00:00 AM | A | PASS |
|
|
fire life safety finaled 9/4/2003 10:24:51 AM
|
FIR03-00090
| INSP-Sprinkler Rough-in/Hydro | 9/3/2003 | 9/4/2003 | 9/4/2003 12:00:00 AM | A | PART |
|
|
Sprinkler piping is ok to cover but the EQ bracing still needs to be completed 9/4/2003 12:07:10 PM
|
FIR03-00390
| INSP-Supply line flush | 9/4/2003 | 9/4/2003 | 9/4/2003 12:00:00 AM | P | PASS |
|
|
Supply line flush is OK 9/4/2003 4:24:29 PM
|
FIR03-00452
| INSP-Final Inspection | 9/4/2003 | 9/4/2003 | 9/4/2003 12:00:00 AM | P | PASS |
|
|
sprinkler piping in place and fire alarm zones to the main fire alarm panel are clear. Main panel is in trouble with a ground fault. Per the property manager the problem is with a circuit board that SimplesGrinnell has on order and will replace 9/4/2003 3:50:04 PM
|
FIR03-00133
| INSP-Sprinkler Rough-in | 9/4/2003 | 9/4/2003 | 9/4/2003 12:00:00 AM | P | FAIL |
|
|
see approved plans for deficiancy locations 9/4/2003 3:39:12 PM
|
BLD02-02471
| FIRE-Final Inspection | 9/4/2003 | 9/4/2003 | 9/4/2003 12:00:00 AM | P | PASS |
|
|
Fire life safety and fire sprinklers finaled 9/4/2003 1:21:11 PM
|
FIR03-00175
| INSP-Final Inspection | 9/4/2003 | 9/4/2003 | 9/4/2003 12:00:00 AM | P | PASS |
|
|
fire sprinklers finaled
|
FIR03-00112
| INSP-Final Inspection | 9/4/2003 | 9/4/2003 | 9/4/2003 12:00:00 AM | P | PASS |
|
|
Underground finaled
|
BLD02-02473
| FIRE-Final Inspection | 9/4/2003 | 9/4/2003 | 9/4/2003 12:00:00 AM | P | PASS |
|
|
Fire life safety, fire alarm and fire sprinklers finaled
|
FIR03-00063
| INSP-Final Inspection | 9/4/2003 | 9/4/2003 | 9/4/2003 12:00:00 AM | P | PASS |
|
|
fire alarm finaled
|
BLD02-02474
| FIRE-Final Inspection | 9/4/2003 | 9/4/2003 | 9/4/2003 12:00:00 AM | P | PASS |
|
|
fire life safety, fire alarm and fire sprinklers finaled
|
FIR03-00064
| INSP-Final Inspection | 9/4/2003 | 9/4/2003 | 9/4/2003 12:00:00 AM | P | PASS |
|
|
fire alarm finaled
|
FIR03-00177
| INSP-Final Inspection | 9/4/2003 | 9/4/2003 | 9/4/2003 12:00:00 AM | P | PASS |
|
|
fire sprinklers finaled
|