ELE07-00799
| Final | 9/4/2007 | 9/4/2007 | 9/4/2007 5:08:23 PM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Sean DeLacy called contr. will will reschedule
|
ELE07-02210
| Electrical Rough-In | 9/3/2007 | 9/4/2007 | 9/4/2007 5:07:51 PM | P | FAIL |
|
|
inspection for ceiling cover Phone #: ###-#### Internet Inspection Request from: Curtis Dunham corr called 110.12(A) seal KOs, 314.25 covers for all boxes, 314.23(D) and 300.11 needs support wires for boxes in grid, bld-0922 support all low voltage cables laying on grid
|
ELE07-03072
| Temporary Service | 9/4/2007 | 9/4/2007 | 9/4/2007 4:22:52 PM | P | PASS |
|
|
chris Phone #: ###-#### t/s o/h new ok
|
ELE07-01704
| Electrical Rough-In | 8/31/2007 | 9/4/2007 | 9/4/2007 3:46:24 PM | P | FAIL |
|
|
larry; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt solar phot ovoltaic system too many things too note owner needs to start over see jf
|
ELE07-02060
| Final | 8/31/2007 | 9/4/2007 | 9/4/2007 3:06:19 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Alan Lusk ok survey posted called box island counter box fill also 110.26(F)(2) for low voltage contr. remove phone and CATV from below p/s
|
ELE07-02294
| Electrical Rough-In | 8/31/2007 | 9/4/2007 | 9/4/2007 2:35:13 PM | P | PASS |
|
|
Reinspection rough-in please. Contact name is Steve Berry. Thank you and have a great day. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw r/i ok corrections made
|
ELE07-02951
| Final | 9/4/2007 | 9/4/2007 | 9/4/2007 2:16:40 PM | P | NH |
|
|
reinspection of sewer pump Phone #: ###-#### Internet Inspection Request from: Celinda Winters called notice posted no one home and pit bulls in yard
|
ELE07-02972
| Final | 9/4/2007 | 9/4/2007 | 9/4/2007 1:48:07 PM | P | PASS |
|
|
Tim; Phone #: ###-#### Internet Inspection Request from: Hattie James ok card signed called needs to label panel
|
ELE07-02131
| Final | 9/4/2007 | 9/4/2007 | 9/4/2007 1:29:46 PM | P | PASS |
|
|
Judy; Phone #: ###-#### Internet Inspection Request from: Hattie James ok needs to correct reversed polarity one bedrm recept
|
ELE07-02753
| Final | 9/4/2007 | 9/4/2007 | 9/4/2007 1:05:57 PM | P | PASS |
|
|
Matt; Phone #: ###-#### Internet Inspection Request from: Hattie James ok no card
|
ELE07-02640
| Electrical Rough-In | 9/4/2007 | 9/4/2007 | 9/4/2007 12:48:28 PM | P | CANC |
|
|
ceiling; Steve; Phone #: ###-#### Internet Inspection Request from: Hattie James ok all ceilings
|
ELE07-02299
| Final | 8/31/2007 | 9/4/2007 | 9/4/2007 11:29:37 AM | A | FAIL |
|
|
Terry; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corr. not made still needs ceiling tiles removed met contr
|
ELE07-02858
| Conference | 8/31/2007 | 9/4/2007 | 9/4/2007 10:51:21 AM | A | DONE |
|
|
David; Phone #: ###-#### Internet Inspection Request from: Hattie James ok
|
ELE07-02732
| Final | 8/31/2007 | 9/4/2007 | 9/4/2007 9:39:48 AM | A | PASS |
|
|
This inspection will be for a cieling and a final please. Marvin Miller is the contact name. Thank you and have a great day. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw ceilings ok final ok card signed
|
ELE07-01691
| Electrical Rough-In | 8/31/2007 | 9/4/2007 | 9/4/2007 9:12:30 AM | A | PART |
|
|
Bud Phone #: ###-#### corridor ceilings anop
|
ELE07-03007
| Final | 8/30/2007 | 9/4/2007 | 9/4/2007 8:44:58 AM | A | CANC |
|
|
Matt; Phone #: ###-#### Internet Inspection Request from: Hattie James x-ray equip shall be field evaluated corr. posted by 432 08-30-07 all parts not listed only control unit. xray generator classified tube backwards RU other components nothing
|