Inspections for the day of: Tuesday, September 4, 2007.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-00799 Final9/4/20079/4/20079/4/2007 5:08:23 PMPCANC
Phone #: ###-#### Internet Inspection Request from: Sean DeLacy called contr. will will reschedule
ELE07-02210 Electrical Rough-In9/3/20079/4/20079/4/2007 5:07:51 PMPFAIL
inspection for ceiling cover Phone #: ###-#### Internet Inspection Request from: Curtis Dunham corr called 110.12(A) seal KOs, 314.25 covers for all boxes, 314.23(D) and 300.11 needs support wires for boxes in grid, bld-0922 support all low voltage cables laying on grid
ELE07-03072 Temporary Service9/4/20079/4/20079/4/2007 4:22:52 PMPPASS
chris Phone #: ###-#### t/s o/h new ok
ELE07-01704 Electrical Rough-In8/31/20079/4/20079/4/2007 3:46:24 PMPFAIL
larry; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt solar phot ovoltaic system too many things too note owner needs to start over see jf
ELE07-02060 Final8/31/20079/4/20079/4/2007 3:06:19 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Alan Lusk ok survey posted called box island counter box fill also 110.26(F)(2) for low voltage contr. remove phone and CATV from below p/s
ELE07-02294 Electrical Rough-In8/31/20079/4/20079/4/2007 2:35:13 PMPPASS
Reinspection rough-in please. Contact name is Steve Berry. Thank you and have a great day. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw
r/i ok corrections made
ELE07-02951 Final9/4/20079/4/20079/4/2007 2:16:40 PMPNH
reinspection of sewer pump Phone #: ###-#### Internet Inspection Request from: Celinda Winters called notice posted no one home and pit bulls in yard
ELE07-02972 Final9/4/20079/4/20079/4/2007 1:48:07 PMPPASS
Tim; Phone #: ###-#### Internet Inspection Request from: Hattie James ok card signed called needs to label panel
ELE07-02131 Final9/4/20079/4/20079/4/2007 1:29:46 PMPPASS
Judy; Phone #: ###-#### Internet Inspection Request from: Hattie James ok needs to correct reversed polarity one bedrm recept
ELE07-02753 Final9/4/20079/4/20079/4/2007 1:05:57 PMPPASS
Matt; Phone #: ###-#### Internet Inspection Request from: Hattie James ok no card
ELE07-02640 Electrical Rough-In9/4/20079/4/20079/4/2007 12:48:28 PMPCANC
ceiling; Steve; Phone #: ###-#### Internet Inspection Request from: Hattie James ok all ceilings
ELE07-02299 Final8/31/20079/4/20079/4/2007 11:29:37 AMAFAIL
Terry; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
corr. not made still needs ceiling tiles removed met contr
ELE07-02858 Conference8/31/20079/4/20079/4/2007 10:51:21 AMADONE
David; Phone #: ###-#### Internet Inspection Request from: Hattie James
ok
ELE07-02732 Final8/31/20079/4/20079/4/2007 9:39:48 AMAPASS
This inspection will be for a cieling and a final please. Marvin Miller is the contact name. Thank you and have a great day.
Phone #: ###-#### Internet Inspection Request from: Laura Longshaw
ceilings ok final ok card signed
ELE07-01691 Electrical Rough-In8/31/20079/4/20079/4/2007 9:12:30 AMAPART
Bud Phone #: ###-#### corridor ceilings anop
ELE07-03007 Final8/30/20079/4/20079/4/2007 8:44:58 AMACANC
Matt; Phone #: ###-#### Internet Inspection Request from: Hattie James x-ray equip shall be field evaluated corr. posted by 432 08-30-07 all parts not listed only control unit. xray generator classified tube backwards RU other components nothing