ELE07-02081
| Final | 9/4/2007 | 9/4/2007 | 9/4/2007 5:09:50 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 9/4/2007 at 11:17:33 AM. Contact: ###-####. corrections made, ok to final
|
ELE07-03024
| Electrical Rough-In | 9/4/2007 | 9/4/2007 | 9/4/2007 4:39:12 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Sean DeLacy walls and hard lids only ok to cover, need address posted
|
ELE07-02532
| Electrical Rough-In | 9/4/2007 | 9/4/2007 | 9/4/2007 4:10:29 PM | P | CANC |
|
|
Scott; Phone #: ###-#### Internet Inspection Request from: Hattie James see conf
|
ELE07-02532
| Conference | 9/4/2007 | 9/4/2007 | 9/4/2007 4:10:08 PM | P | DONE |
|
|
Scott; Phone #: ###-#### Internet Inspection Request from: Hattie James owner not ready, too many corrections, reviewed problem areas, he is going to change scope of work and update permit to include service change, talked about prepare concrete encased electrode before pour, 370 said ok to cover u/g for part of driveway where service from house is coming from
|
ELE06-02660
| Final | 9/4/2007 | 9/4/2007 | 9/4/2007 3:21:42 PM | P | PASS |
|
|
Dave is owner; contractor out of town; Phone #: ###-#### Internet Inspection Request from: Hattie James talked with owner and contr, need to add 2 recpts , id bkr in panel and tighten 1 recpt, ok to final
|
ELE07-03068
| Temporary Service | 9/4/2007 | 9/4/2007 | 9/4/2007 3:00:55 PM | P | FAIL |
|
|
todd Phone #: ###-#### called, nec 250.53(G) electrode shall be flush with ground, 230.23(B)(4) minimum clearance shall be 18 ft above grade in alley, 230.2 shall supply building with only 1 service, BCC shall provide min 120 and 250 volt recpts with gfci protection
|
ELE07-02470
| Final | 9/4/2007 | 9/4/2007 | 9/4/2007 2:36:11 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman ok to final, signed occ card
|
ELE07-01557
| Permanent Service | 8/28/2007 | 9/4/2007 | 9/4/2007 1:55:10 PM | P | PASS |
|
|
Chris; Phone #: ###-#### Internet Inspection Request from: Hattie James met owner, check sub-panels for ground isolation at ri, p/s u/g rec ok
|
ELE07-02466
| Final | 8/29/2007 | 9/4/2007 | 9/4/2007 1:45:50 PM | P | PASS |
|
|
James; Phone #: ###-#### Internet Inspection Request from: Hattie James called to label un-labelled breakers, ok to final
|
ELE07-03070
| Rough-In Permanent Service | 9/4/2007 | 9/4/2007 | 9/4/2007 1:15:23 PM | P | FAIL |
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Hattie James called, nec 312.5 shall provide abrasion protection for all conductors entering enclosure, 550.32(B) shall meet all criteria for this part of article ( mfgrs instruction to allow service on structure) 250.52(A)(3) concrete encased electrode sahll be provided
|
ELE07-03067
| Permanent Service | 9/4/2007 | 9/4/2007 | 9/4/2007 12:47:50 PM | P | PASS |
|
|
mitch Phone #: ###-#### called, left message to label breakers not identified, p/s o/h rec ok
|
ELE07-02982
| Rough-In Permanent Service | 9/4/2007 | 9/4/2007 | 9/4/2007 12:02:39 PM | A | PASS |
|
|
Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ric ok, p/s u/g n ok
|
ELE07-01936
| Final | 8/31/2007 | 9/4/2007 | 9/4/2007 11:06:41 AM | A | PASS |
|
|
Ted or Boyd @###-#### are on-site contacts. Thanks Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa ok to final, signed struct card
|
ELE07-01624
| Electrical Rough-In | 9/4/2007 | 9/4/2007 | 9/4/2007 10:32:23 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 9/4/2007 at 7:21:11 AM. Contact: ###-####. walls only anop ok to cover
|
ELE07-03024
| Electrical Rough-In | 9/4/2007 | 9/4/2007 | 9/4/2007 10:09:23 AM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Sean DeLacy Inspection cancelled from web by: Sean DeLacy
|
ELE07-03060
| Rough-In Permanent Service | 8/31/2007 | 9/4/2007 | 9/4/2007 10:01:51 AM | A | PASS |
|
|
###-#### called contr, about recpts, nail plates, ric ok , p/s u/g n ok
|
ELE07-02684
| Final | 9/4/2007 | 9/4/2007 | 9/4/2007 9:17:13 AM | A | PASS |
|
|
###-#### Internet Inspection Request from: Todd Holbrook ok to final, signed occ card
|
ELE07-02684
| Permanent Service | 9/4/2007 | 9/4/2007 | 9/4/2007 9:16:35 AM | A | PASS |
|
|
###-#### Internet Inspection Request from: Todd Holbrook p/s u/g rec ok, electrodes ok
|
ELE07-02963
| Electrical Rough-In | 8/31/2007 | 9/4/2007 | 9/4/2007 8:49:47 AM | A | PART |
|
|
Underground Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton told elect to get set of prints for marking, ok to cover inside perimeter along walls
|
ELE07-03039
| Electrical Rough-In | 8/31/2007 | 9/4/2007 | 9/4/2007 8:26:27 AM | A | PASS |
|
|
potting & bonding-luis; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt ok to pour equipot plane and potting ok to pour
|
ELE07-02547
| Final | 8/31/2007 | 9/4/2007 | 9/4/2007 8:01:51 AM | A | PART |
|
|
Contact is Perry. Final inspection for Bakery Dept. only. Phone #: ###-#### Internet Inspection Request from: David Bonner ok to cover bakery clg except cooler area only, signed plan in office
|
ELE07-02684
| Permanent Service | 8/31/2007 | 9/4/2007 | 9/4/2007 7:18:48 AM | P | CANC |
|
|
###-#### Internet Inspection Request from: Todd Holbrook Inspection cancelled from web by: Todd Holbrook
|
ELE07-02684
| Final | 8/31/2007 | 9/4/2007 | 9/4/2007 7:18:44 AM | P | CANC |
|
|
###-#### Internet Inspection Request from: Todd Holbrook Inspection cancelled from web by: Todd Holbrook
|