FIR07-00441
| INSP-Final Inspection | 8/31/2007 | 9/4/2007 | 9/4/2007 4:41:43 PM | A | NR |
|
|
sandy; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt
|
FIR07-00664
| INSP-Alarm Testing | 8/31/2007 | 9/4/2007 | 9/4/2007 4:39:50 PM | A | FAIL |
|
|
The SD at the new control panel is too close to an HVAC supply register, one duct detector has the sample tube installed backward, need to locate the inspectors test valve to enable testing of the sprinkler flow switch, the existing FACP if no longer in service shall be removed to prevent confusion, need to verify signals at the supervising station.
|
FIR07-00304
| INSP-Sprinkler Rough-in | 9/4/2007 | 9/4/2007 | 9/4/2007 3:00:36 PM | P | DEFR |
|
|
Inspection rescheduled for 9/5 as discussed.
|
BLD06-01188
| FIRE-Conference | 8/29/2007 | 9/4/2007 | 9/4/2007 2:42:39 PM | A | DONE |
|
|
Discussion regarding atrium smoke evac testing and stairwell pressure test.
|
BLD07-00959
| FIRE-Final Inspection | 8/31/2007 | 9/4/2007 | 9/4/2007 2:28:58 PM | P | NR |
|
|
Pending project related fire sprinkler permit final.
|
FIR07-00437
| INSP-Sprinkler Rough-in | 9/4/2007 | 9/4/2007 | 9/4/2007 2:16:49 PM | P | PART |
|
|
Circled areas on stamped plan set okayed for cover, noted one overspaced head at the corridor, remainder of the scope of work is not complete.
|
BLD07-00297
| FIRE-Final Inspection | 8/31/2007 | 9/4/2007 | 9/4/2007 2:14:02 PM | A | PASS |
|
|
Fire life safety passed field inspection.
|
FIR07-00220
| INSP-Final Inspection | 9/4/2007 | 9/4/2007 | 9/4/2007 2:12:52 PM | P | PASS |
|
|
Final fire sprinkler inspection passed, permit finaled.
|
FIR07-00015
| INSP-Alarm Testing | 8/30/2007 | 9/4/2007 | 9/4/2007 2:11:02 PM | A | PART |
|
|
See approved plans for areas tested today, noted some floor plan modifications affecting alarm work, need to add devices as noted, addressing has changed at some locations and is recorded on as-builts.
|
FIR07-00204
| INSP-Sprinkler Rough-in/Hydro | 8/31/2007 | 9/4/2007 | 9/4/2007 2:06:55 PM | A | PART |
|
|
Hydrostatic testing for the first and second floors passed, the third floor hydro failed due to pressure loss at the guage.
|
FIR07-00147
| FIR-Aging Inspection | 9/4/2007 | 9/4/2007 | 9/4/2007 10:39:11 AM | | DEFR |
|
|
Work in progress.
|
BLD07-01644
| FIRE-Final Inspection | 8/31/2007 | 9/4/2007 | 9/4/2007 10:34:26 AM | A | PASS |
|
|
Fire life safety finaled.
|
FIR07-00015
| INSP-Alarm Testing | 8/30/2007 | 9/4/2007 | 8/30/2007 11:59:03 AM | A | CANC |
|
|
Forrest,
This is a confirmation of rescheduling a partial inspection of in-patient pharmacy at St. Luke''s Hospital from today to next Tuesday, 9-4-07 due to inspection backlog. Please call for time.
Thanks,
Jim Phone #: ###-#### Internet Inspection Request from: James Shilton Inspection cancelled from web by: James Shilton
|