Inspections for the day of: Tuesday, September 4, 2007.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00011 INSP-Alarm Testing9/4/20079/4/20079/5/2007 9:02:20 AMPFAIL
One of the new a/v's in the exam room did not function at all, mount the existing devices at code driven heights as per the approved drawings and provide manometer testing of the duct smoke detectors as per the previous correction list. Duct detectors will need to be tested for functionality as well.
FIR05-00536 INSP-Final Inspection9/4/20079/4/20079/4/2007 3:43:10 PMPFAIL
We had a key for access but ceiling tile was missing from every room. The inspection was stopped after the fifth room. This was on the first floor.
BLD07-01764 FIRE-Final Inspection9/4/20079/4/20079/4/2007 3:37:43 PMPFAIL
Provide panic hardware on the rear exit door as per the approved plans or get permission from the plan reviewer that lever hardware is ok. All other items are ok.
FIR07-00610 INSP-Final Inspection9/4/20079/4/20079/4/2007 3:16:49 PMPFAIL
Supply registers are located less than 1' to the sprinkler pendants. Per the fitter these registers will be moved.
BLD06-02674 FIRE-Final Inspection8/31/20079/4/20079/4/2007 3:09:13 PMPFAIL
Repair the exit discharge light at the main exit and repair the exit sign as marked on the plans. Shell permit needs to be finaled as well.
FIR06-00708 INSP-Final Inspection9/3/20079/4/20079/4/2007 2:16:16 PMAPASS
Permit finaled
BLD07-00427 FIRE-Final Inspection9/4/20079/4/20079/4/2007 2:13:34 PMPFAIL
Provide verification that the hydrant that has been relocated from murano ct. to owhyee street is approved to be in the new location. Provide the "compact" parking striping for fire dept access verification. Remove covers from the fire extinguishers. Provide the apartment numbers. Set up the exit doors to close from a partially open position. Provide the missing smoke alarms outside of the bedroom as shown on the plans.
BLD07-02377 FIRE-Final Inspection9/4/20079/4/20079/4/2007 1:09:01 PMPPASS
life safety passed
FIR06-00957 INSP-Final Inspection8/31/20079/4/20079/4/2007 1:03:19 PMAFAIL
The final inspecton for the third floor of A wing was started today. I found that instead of viking pendants being installed reliable pendants had been installed. Also many of the light fixtures are blocking the pendant heads in the laundry/utility romms and in the main corridor.
FIR06-00956 INSP-Final Inspection8/31/20079/4/20079/4/2007 1:01:11 PMAFAIL
The final inspecton for the third floor of A wing was started today. I found that instead of viking pendants being installed reliable pendants had been installed. Also many of the light fixtures are blocking the pendant heads in the laundry/utility romms and in the main corridor.
FIR06-00958 INSP-Final Inspection8/31/20079/4/20079/4/2007 12:57:43 PM FAIL
The final inspecton for the third floor of A wing was started today. I found that instead of viking pendants being installed reliable pendants had been installed. Also many of the light fixtures are blocking the pendant heads in the laundry/utility romms and in the main corridor. Need to change out heads or resubmit as built plans and data sheets for verification of hydraulic calcs and head spacing. Also need data sheets for the dry s/w heads to verify installation distance below ceilings on patios.
BLD05-00633 FIRE-Final Inspection8/31/20079/4/20079/4/2007 12:51:03 PMACANC
I left a message with Toms secretary that I would not perform the life safety inspection until the alarm and fire sprinkler permits have been completed as was previously stated.
FIR06-00811 INSP-Final Inspection8/31/20079/4/20079/4/2007 12:25:55 PMACANC
No alarm inspection performed today. Just sprinklers were looked at.
FIR06-00813 INSP-Final Inspection8/31/20079/4/20079/4/2007 12:23:17 PMACANC
No alarm inspection performed today. Just sprinklers were looked at.
FIR06-00812 INSP-Final Inspection8/31/20079/4/20079/4/2007 12:21:21 PMACANC
No alarm inspection performed today. Just sprinklers were looked at.
BLD07-00913 FIRE-Final Inspection8/31/20079/4/20079/4/2007 12:15:30 PMAPASS
Life safety passed.