FIR06-00011
| INSP-Alarm Testing | 9/4/2007 | 9/4/2007 | 9/5/2007 9:02:20 AM | P | FAIL |
|
|
One of the new a/v's in the exam room did not function at all, mount the existing devices at code driven heights as per the approved drawings and provide manometer testing of the duct smoke detectors as per the previous correction list. Duct detectors will need to be tested for functionality as well.
|
FIR05-00536
| INSP-Final Inspection | 9/4/2007 | 9/4/2007 | 9/4/2007 3:43:10 PM | P | FAIL |
|
|
We had a key for access but ceiling tile was missing from every room. The inspection was stopped after the fifth room. This was on the first floor.
|
BLD07-01764
| FIRE-Final Inspection | 9/4/2007 | 9/4/2007 | 9/4/2007 3:37:43 PM | P | FAIL |
|
|
Provide panic hardware on the rear exit door as per the approved plans or get permission from the plan reviewer that lever hardware is ok. All other items are ok.
|
FIR07-00610
| INSP-Final Inspection | 9/4/2007 | 9/4/2007 | 9/4/2007 3:16:49 PM | P | FAIL |
|
|
Supply registers are located less than 1' to the sprinkler pendants. Per the fitter these registers will be moved.
|
BLD06-02674
| FIRE-Final Inspection | 8/31/2007 | 9/4/2007 | 9/4/2007 3:09:13 PM | P | FAIL |
|
|
Repair the exit discharge light at the main exit and repair the exit sign as marked on the plans. Shell permit needs to be finaled as well.
|
FIR06-00708
| INSP-Final Inspection | 9/3/2007 | 9/4/2007 | 9/4/2007 2:16:16 PM | A | PASS |
|
|
Permit finaled
|
BLD07-00427
| FIRE-Final Inspection | 9/4/2007 | 9/4/2007 | 9/4/2007 2:13:34 PM | P | FAIL |
|
|
Provide verification that the hydrant that has been relocated from murano ct. to owhyee street is approved to be in the new location. Provide the "compact" parking striping for fire dept access verification. Remove covers from the fire extinguishers. Provide the apartment numbers. Set up the exit doors to close from a partially open position. Provide the missing smoke alarms outside of the bedroom as shown on the plans.
|
BLD07-02377
| FIRE-Final Inspection | 9/4/2007 | 9/4/2007 | 9/4/2007 1:09:01 PM | P | PASS |
|
|
life safety passed
|
FIR06-00957
| INSP-Final Inspection | 8/31/2007 | 9/4/2007 | 9/4/2007 1:03:19 PM | A | FAIL |
|
|
The final inspecton for the third floor of A wing was started today. I found that instead of viking pendants being installed reliable pendants had been installed. Also many of the light fixtures are blocking the pendant heads in the laundry/utility romms and in the main corridor.
|
FIR06-00956
| INSP-Final Inspection | 8/31/2007 | 9/4/2007 | 9/4/2007 1:01:11 PM | A | FAIL |
|
|
The final inspecton for the third floor of A wing was started today. I found that instead of viking pendants being installed reliable pendants had been installed. Also many of the light fixtures are blocking the pendant heads in the laundry/utility romms and in the main corridor.
|
FIR06-00958
| INSP-Final Inspection | 8/31/2007 | 9/4/2007 | 9/4/2007 12:57:43 PM | | FAIL |
|
|
The final inspecton for the third floor of A wing was started today. I found that instead of viking pendants being installed reliable pendants had been installed. Also many of the light fixtures are blocking the pendant heads in the laundry/utility romms and in the main corridor. Need to change out heads or resubmit as built plans and data sheets for verification of hydraulic calcs and head spacing. Also need data sheets for the dry s/w heads to verify installation distance below ceilings on patios.
|
BLD05-00633
| FIRE-Final Inspection | 8/31/2007 | 9/4/2007 | 9/4/2007 12:51:03 PM | A | CANC |
|
|
I left a message with Toms secretary that I would not perform the life safety inspection until the alarm and fire sprinkler permits have been completed as was previously stated.
|
FIR06-00811
| INSP-Final Inspection | 8/31/2007 | 9/4/2007 | 9/4/2007 12:25:55 PM | A | CANC |
|
|
No alarm inspection performed today. Just sprinklers were looked at.
|
FIR06-00813
| INSP-Final Inspection | 8/31/2007 | 9/4/2007 | 9/4/2007 12:23:17 PM | A | CANC |
|
|
No alarm inspection performed today. Just sprinklers were looked at.
|
FIR06-00812
| INSP-Final Inspection | 8/31/2007 | 9/4/2007 | 9/4/2007 12:21:21 PM | A | CANC |
|
|
No alarm inspection performed today. Just sprinklers were looked at.
|
BLD07-00913
| FIRE-Final Inspection | 8/31/2007 | 9/4/2007 | 9/4/2007 12:15:30 PM | A | PASS |
|
|
Life safety passed.
|