Inspections for the day of: Wednesday, September 4, 2019.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-03923 FIRE-Final Inspection9/4/20199/4/20199/4/2019 3:19:00 PMPPASS
Life safety passed. Card signed. Brandon Phone #: ###-####
FIR19-00653 INSP-Final Inspection9/4/20199/4/20199/4/2019 3:18:08 PMPFAIL
Need to relocate the two manual pull stations to the 10' - 20' min. max. Need shield between fryer and oven. No testing performed. zack Phone #: ###-####
BLD18-03121 FIRE-Final Inspection9/3/20199/4/20199/4/2019 2:05:22 PMACANC
Life safety will be a pass for the north most apartments when the project related fire alarm and fire sprinkler permits are passed. Matt- mid mornign Phone #: ###-####
FIR19-00309 INSP-Final Inspection9/3/20199/4/20199/4/2019 2:04:32 PMAFAIL
Today's inspection had it passed would be only for the six north most apartments. However two of the three flow switches did not function. Still need to test the crawl space tamper switches.


Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00203 INSP-Final Inspection9/3/20199/4/20199/4/2019 2:01:25 PMAFAIL
Two fo the three flow switches did not function. Still need to test the crawl space tamper switches.

We would like 9:30am if that is possible. Phone #: ###-#### Inspection requested via web by Fire Scheduler
FIR19-00461 INSP-Final Inspection9/3/20199/4/20199/4/2019 12:28:18 PMAPART
A temporary for this permit is being given until an upgrade agreement has been finalized with the Boise Fire Dept for the fire alarm system.

This inspection needs to be before 7:30 am as this is a school and they will be in session. Please call ahead to Brian @ ###-####. Phone #: ###-#### Inspection requested via web by Kristin Dolan
NAF19-00074 INSP-Sprinkler Rough-in/Hydro9/3/20199/4/20199/4/2019 10:50:07 AMAPASS
Overhead rough-in, tenting and hydro passed. Piping is ok for cover. Well supply piping not provided yet.

Call prior to going Phone #: 2083910988 >> Inspection requested via mobile web by Anthony Minichiello
BLD19-02940 FIRE-Final Inspection9/3/20199/4/20199/4/2019 9:27:10 AMAPASS
life safety passed. Card signed.

ask for Sue // Duane Phone #: ###-####
FIR19-00511 INSP-Sprinkler Rough-in9/3/20199/4/20199/4/2019 12:00:00 AMPPART
**Partial Rough Inspection Pass** Inspection of pipe hangers prior to the installation of roof insulation**MAS**
Kenny Caldwell is the contact. This is to be a rough-in hanger inspection. Thank you for your hard work! Phone #: ###-#### >> Inspection requested via web by Stan Beus