FIR19-00523
| INSP-Final Inspection | 9/4/2019 | 9/4/2019 | 9/4/2019 2:30:15 PM | P | PASS |
|
|
Automatic shutoff valve for gas was installed backwards, not wiht the flow as indicated on the housing of valve. A new valve has been installed with the correct direction and gas shutoff happened with hood suppression system activation. Final inspection for hood suppression system complete.
|
BLD19-01714
| FIRE-Final Inspection | 9/4/2019 | 9/4/2019 | 9/4/2019 2:05:01 PM | P | CANC |
|
|
Cancelled per conversation with point of contact due to signage requirements not in place, rescheduled for 05SEPT2019.
dALE Phone #: ###-####
|
BLD18-04579
| FIRE-Final Inspection | 9/4/2019 | 9/4/2019 | 9/4/2019 2:05:00 PM | P | PASS |
|
|
Final life fire safety inspection for area of work complete, signature card not available for signature.
dALE Phone #: ###-####
|
BLD19-01074
| FIRE-Final Inspection | 9/4/2019 | 9/4/2019 | 9/4/2019 12:04:40 PM | P | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for are of work complete.
per 415
|
FIR19-00255
| INSP-Final Inspection | 9/4/2019 | 9/4/2019 | 9/4/2019 11:21:31 AM | A | FAIL |
|
|
Basement fire sprinkler system is not noted on the city approved drawings. Install does not match city approved draiwngs, discussed areas that is lacking coverage in the vestibules leading to the restrooms.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR19-00363
| INSP-Final Inspection | 9/3/2019 | 9/4/2019 | 9/4/2019 9:36:46 AM | A | PASS |
|
|
Final fire alarm ibnspection for area of work complete.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
BLD19-03336
| FIRE-Final Inspection | 9/3/2019 | 9/4/2019 | 9/4/2019 8:53:17 AM | A | PASS |
|
|
Previously noted item has been correted, new batteries were being installed in exit lights at time of inspection. No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags. Final life fire safety inspection complete, card has been signed.
Melissa Phone #: ###-####
|
FIR19-00523
| INSP-Final Inspection | 9/3/2019 | 9/4/2019 | 9/4/2019 8:17:30 AM | A | FAIL |
|
|
Still have gas flowing after hood suppression system activation and gas valve automatic shutoff has been actuated.
Phone #: 2086157641 >> Inspection requested via mobile web by Richard Johnson
|