Inspections for the day of: Wednesday, September 4, 2019.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00523 INSP-Final Inspection9/4/20199/4/20199/4/2019 2:30:15 PMPPASS
Automatic shutoff valve for gas was installed backwards, not wiht the flow as indicated on the housing of valve. A new valve has been installed with the correct direction and gas shutoff happened with hood suppression system activation. Final inspection for hood suppression system complete.
BLD19-01714 FIRE-Final Inspection9/4/20199/4/20199/4/2019 2:05:01 PMPCANC
Cancelled per conversation with point of contact due to signage requirements not in place, rescheduled for 05SEPT2019.

dALE Phone #: ###-####
BLD18-04579 FIRE-Final Inspection9/4/20199/4/20199/4/2019 2:05:00 PMPPASS
Final life fire safety inspection for area of work complete, signature card not available for signature.

dALE Phone #: ###-####
BLD19-01074 FIRE-Final Inspection9/4/20199/4/20199/4/2019 12:04:40 PMPPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for are of work complete.

per 415
FIR19-00255 INSP-Final Inspection9/4/20199/4/20199/4/2019 11:21:31 AMAFAIL
Basement fire sprinkler system is not noted on the city approved drawings. Install does not match city approved draiwngs, discussed areas that is lacking coverage in the vestibules leading to the restrooms.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
FIR19-00363 INSP-Final Inspection9/3/20199/4/20199/4/2019 9:36:46 AMAPASS
Final fire alarm ibnspection for area of work complete.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
BLD19-03336 FIRE-Final Inspection9/3/20199/4/20199/4/2019 8:53:17 AMAPASS
Previously noted item has been correted, new batteries were being installed in exit lights at time of inspection. No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags. Final life fire safety inspection complete, card has been signed.

Melissa Phone #: ###-####
FIR19-00523 INSP-Final Inspection9/3/20199/4/20199/4/2019 8:17:30 AMAFAIL
Still have gas flowing after hood suppression system activation and gas valve automatic shutoff has been actuated.

Phone #: 2086157641 >> Inspection requested via mobile web by Richard Johnson