Inspections for the day of: Thursday, September 5, 2002.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-01263 FIRE-Final Inspection9/4/20029/5/20029/5/2002 12:00:00 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung need door hardware completed; per Dave Miller a temp occ can be issued if door hardware is completed; alarm plans not submitted as of today; will need to verify duct detectors/ alarms plans for permanent occ 9/5/2002 4:02:48 PM
FIR02-00005 INSP-Sprinkler Rough-in/Hydro9/4/20029/5/20029/5/2002 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 09/04/2002 at 13:28:58. Contact: ###-####. heads obstructed/overspaced in basement mechanical; refer room; janitor room; EQ branch line in south room; add line and head in south room as shown on plans; heads painted in computer room; heads fire proofed in service corridor; temp walk way off concourse okay to cover; combustibles in concealed space by phone area; okay to cover mechanical chase on third floor 9/5/2002 11:05:16 AM
BLD02-00331 FIRE-Final Inspection9/5/20029/5/20029/5/2002 12:00:00 AMPPASS
RON; Phone #: ###-#### Internet Inspection Request from: Annette Moore
BLD02-01278 FIRE-Final Inspection9/5/20029/5/20029/5/2002 12:00:00 AMPPASS
fire fn rich- ###-####