Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00159 FIR-Aging Inspection9/5/20039/5/20039/5/2003 12:00:00 AM PASS
this building is still under construction 9/5/2003 7:18:41 AM
BLD03-01769 FIRE-Final Inspection9/5/20039/5/20039/5/2003 12:00:00 AMAPASS
FIR03-00289 INSP-Supply line flush9/5/20039/5/20039/5/2003 12:00:00 AMAPASS
UG flush okay 9/5/2003 11:33:57 AM
FIR03-00369 INSP-Supply line flush9/4/20039/5/20039/5/2003 12:00:00 AMACANC
Scheduled by a contractor via Hello! on 9/4/2003 at 2:38:49 PM. Contact: ###-####. wrong permit called in -see FIR03-00289 for flush 9/5/2003 9:41:15 AM
BLD03-01482 FIRE-Final Inspection9/4/20039/5/20039/5/2003 12:00:00 AMAPASS
richard; Phone #: ###-#### Internet Inspection Request from: Annette Moore
BLD03-01082 FIRE-Final Inspection9/4/20039/5/20039/5/2003 12:00:00 AMAPASS
richard; Phone #: ###-#### Internet Inspection Request from: Annette Moore
BLD03-01053 FIRE-Final Inspection9/4/20039/5/20039/5/2003 12:00:00 AMAPASS
10 am duct detectors tested okay - perm occ okay 9/5/2003 10:29:08 AM
FIR03-00464 INSP-Final Inspection9/4/20039/5/20039/5/2003 12:00:00 AMAPASS
jim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
BLD03-01553 FIRE-Final Inspection9/4/20039/5/20039/5/2003 12:00:00 AMPNR
jim; Phone #: ###-#### Internet Inspection Request from: Marc Lileks will be rescheduled 9/5/2003 4:15:57 PM
FIR03-00347 INSP-Sprinkler Rough-in9/4/20039/5/20039/5/2003 12:00:00 AMPFAIL
ross; Phone #: ###-#### Internet Inspection Request from: Barbara Moore attic heads overspaced in classrooms; attic heads not 16-22 inches drom ridge; deflector on hip heads turned the wrong way; sprigs not supported; attic area not protected in north side room; heads within 6 ft in rooms with moveable partitions; return bends not used in all areas; area under stairs and under stage require sprinkler protection; FDC obstrcuted by bushes; not approved for cover 9/5/2003 4:23:11 PM
BLD03-00926 FIRE-Supply Line Hydro9/4/20039/5/20039/5/2003 12:00:00 AMPCANC
Scheduled by a contractor via Hello! on 9/4/2003 at 4:45:41 PM. Contact: ###-####. wrong type inspection called in; fire not required for sign off 9/5/2003 4:17:05 PM
BLD03-01681 FIRE-Final Inspection9/5/20039/5/20039/5/2003 12:00:00 AMPPASS
JIM; Phone #: ###-#### Internet Inspection Request from: Marc Lileks
MIS03-00166 FIR-Final9/5/20039/5/20039/5/2003 12:00:00 AMPPASS
gail -###-####- call 1st before insp the fire sprinkler monitoring will require and smoke above panel, manual pull and audible alarm; a remodel is under design and will be permited and at that time the panel will be brought up to code 9/5/2003 2:07:07 PM