FIR03-00159
| FIR-Aging Inspection | 9/5/2003 | 9/5/2003 | 9/5/2003 12:00:00 AM | | PASS |
|
|
this building is still under construction 9/5/2003 7:18:41 AM
|
BLD03-01769
| FIRE-Final Inspection | 9/5/2003 | 9/5/2003 | 9/5/2003 12:00:00 AM | A | PASS |
|
|
|
FIR03-00289
| INSP-Supply line flush | 9/5/2003 | 9/5/2003 | 9/5/2003 12:00:00 AM | A | PASS |
|
|
UG flush okay 9/5/2003 11:33:57 AM
|
FIR03-00369
| INSP-Supply line flush | 9/4/2003 | 9/5/2003 | 9/5/2003 12:00:00 AM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 9/4/2003 at 2:38:49 PM. Contact: ###-####. wrong permit called in -see FIR03-00289 for flush 9/5/2003 9:41:15 AM
|
BLD03-01482
| FIRE-Final Inspection | 9/4/2003 | 9/5/2003 | 9/5/2003 12:00:00 AM | A | PASS |
|
|
richard; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
BLD03-01082
| FIRE-Final Inspection | 9/4/2003 | 9/5/2003 | 9/5/2003 12:00:00 AM | A | PASS |
|
|
richard; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
BLD03-01053
| FIRE-Final Inspection | 9/4/2003 | 9/5/2003 | 9/5/2003 12:00:00 AM | A | PASS |
|
|
10 am duct detectors tested okay - perm occ okay 9/5/2003 10:29:08 AM
|
FIR03-00464
| INSP-Final Inspection | 9/4/2003 | 9/5/2003 | 9/5/2003 12:00:00 AM | A | PASS |
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
BLD03-01553
| FIRE-Final Inspection | 9/4/2003 | 9/5/2003 | 9/5/2003 12:00:00 AM | P | NR |
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Marc Lileks will be rescheduled 9/5/2003 4:15:57 PM
|
FIR03-00347
| INSP-Sprinkler Rough-in | 9/4/2003 | 9/5/2003 | 9/5/2003 12:00:00 AM | P | FAIL |
|
|
ross; Phone #: ###-#### Internet Inspection Request from: Barbara Moore attic heads overspaced in classrooms; attic heads not 16-22 inches drom ridge; deflector on hip heads turned the wrong way; sprigs not supported; attic area not protected in north side room; heads within 6 ft in rooms with moveable partitions; return bends not used in all areas; area under stairs and under stage require sprinkler protection; FDC obstrcuted by bushes; not approved for cover 9/5/2003 4:23:11 PM
|
BLD03-00926
| FIRE-Supply Line Hydro | 9/4/2003 | 9/5/2003 | 9/5/2003 12:00:00 AM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 9/4/2003 at 4:45:41 PM. Contact: ###-####. wrong type inspection called in; fire not required for sign off 9/5/2003 4:17:05 PM
|
BLD03-01681
| FIRE-Final Inspection | 9/5/2003 | 9/5/2003 | 9/5/2003 12:00:00 AM | P | PASS |
|
|
JIM; Phone #: ###-#### Internet Inspection Request from: Marc Lileks
|
MIS03-00166
| FIR-Final | 9/5/2003 | 9/5/2003 | 9/5/2003 12:00:00 AM | P | PASS |
|
|
gail -###-####- call 1st before insp the fire sprinkler monitoring will require and smoke above panel, manual pull and audible alarm; a remodel is under design and will be permited and at that time the panel will be brought up to code 9/5/2003 2:07:07 PM
|