Inspections for the day of: Tuesday, September 5, 2006.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-02051 ELE-Aging Inspection9/5/20069/5/20069/7/2006 2:10:10 PM PART
wsuc
ELE06-02666 Final9/5/20069/5/20069/5/2006 4:00:20 PMPFAIL
neil ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. called panel schedule shall be specific, install MB closet fixture
ELE06-02207 Final9/5/20069/5/20069/5/2006 3:42:37 PMPFAIL
ted ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr. called
410.8 clearence MB closet, 210.52(C)(5) except. outlet peninsular counter right of sink more than 6 ", 408.4 needs specific circuit directory, 314.29 entry light box buried
ELE06-02345 Final9/5/20069/5/20069/5/2006 2:57:31 PMPPASS
Garage code 1974; Phone #: ###-#### Internet Inspection Request from: Therrin Robertson
ELE06-01454 Final9/5/20069/5/20069/5/2006 2:57:16 PMPPASS
Garage code 1974; Phone #: ###-#### Internet Inspection Request from: Therrin Robertson
ELE06-01275 Electrical Rough-In9/5/20069/5/20069/5/2006 2:15:36 PMPPART
This inspection will be for a partical rough in. Please ask for Marvin Miller.; Phone #: ###-#### Internet Inspection Request from: Laura Longshaw S. stairwell ok
ELE06-02976 Electrical Rough-In8/30/20069/5/20069/5/2006 12:48:35 PMAFAIL
Sergey; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
corr. met owner 210.52(A) needs outlet 2ft wall MBed rm, 410.8 clearence MB closet, 210.11(C)(3) shall provide required circuit, or circuits for bath rms, 300.4 (A)(1)&(D) prvide nail plates and 11/4" 210.70 (A)(2) (b) switch at exit door for outside light, 220.12&16 shall calc out reqired circuits for new addition, 408.41 only 1 neutral per terminal , B C C complete all makeup and grd pigtails for recepts and switches
ELE06-00720 Final9/1/20069/5/20069/5/2006 10:37:34 AMAFAIL
Enter through man door at East side of garage.; Phone #: ###-#### Internet Inspection Request from: Joe Thomas
corr. called box fill island 314.16, tottally enclosed fixture NE bed rm closet upstairs
ELE06-02092 Final9/1/20069/5/20069/5/2006 9:42:29 AMACANC
steve; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
contractor called nr, inspection was called in by owner
ELE06-00711 Electrical Rough-In8/31/20069/5/20069/5/2006 9:17:33 AMAPART
Scheduled by a contractor via Hello! on 8/31/2006 at 3:05:49 PM. Contact: ###-####. 3rd floor anop walls, needs to remove duct over panels
ELE06-02784 Final9/1/20069/5/20069/5/2006 7:50:33 AMAPASS
meet owner between 7:30,and 8:00 AM ok
ELE06-03173 Permanent Service9/1/20069/5/20069/1/2006 4:33:58 PMACANC
Joe; Phone #: ###-#### Internet Inspection Request from: Joseph Zumwalt Inspection cancelled from web by: Joseph Zumwalt