Inspections for the day of: Tuesday, September 5, 2006.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-02002 Final9/5/20069/5/20069/5/2006 4:43:18 PMPPASS
ted - call prior for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final
ELE05-01557 Final9/5/20069/5/20069/5/2006 3:48:33 PMPPASS
Daniel; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt told owner to install in-use covers, ok to final
ELE06-03275 Conference9/5/20069/5/20069/5/2006 2:57:30 PMPCANC
Scheduled by a contractor via Hello! on 9/5/2006 at 11:11:42 AM. Contact: ###-####. wrong permit, see ele06-02254
ELE06-02413 ELE-Aging Inspection9/5/20069/5/20069/5/2006 2:44:05 PM DONE
called, suc
ELE06-02254 Electrical Rough-In9/5/20069/5/20069/5/2006 2:23:40 PMPPART
6 recessed lites in front hard lid ok to cover, talked about fixtures not being suitable for purpose for outside as requested on plans
ELE06-00381 Final9/5/20069/5/20069/5/2006 2:20:35 PMPPASS
corr made, ok to final
ELE06-02906 Final9/5/20069/5/20069/5/2006 1:46:54 PMPFAIL
craig ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called, left corr notice, nec 210.8(A)(2),(3) all receptacles on 15 or 20a circuits shall have gfci protection, 406.8(B) outside receptacles shall have weatherproof covers whether or not plug is inserted
ELE06-03252 Electrical Rough-In9/5/20069/5/20069/5/2006 1:27:13 PMPPASS
andry ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr made, ric ok
ELE06-03110 Electrical Rough-In9/5/20069/5/20069/5/2006 10:54:05 AMAPASS
ric ok, talked about outlet space, p/s u/g n ok
ELE06-03191 Final8/25/20069/5/20069/5/2006 10:49:15 AMAPASS
Dan ###-#### //also has 7 low voltage fixtures told owner to change address to 12386, ok to final
ELE06-03191 Conference8/25/20069/5/20069/5/2006 10:48:31 AMADONE
Dan ###-#### told owner to change address to 12386, talked about strobes for some areas
ELE06-03252 Conference8/30/20069/5/20069/5/2006 10:47:26 AMACANC
andry ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley see ri
ELE06-03252 Electrical Rough-In9/5/20069/5/20069/5/2006 10:47:08 AMAFAIL
andry ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley nec 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing member
ELE06-01232 Final9/1/20069/5/20069/5/2006 9:41:04 AMAPASS
CONTACT: SHANE KORTE; Phone #: ###-#### Internet Inspection Request from: Deb McCoy talked to elect about closet lite,disp cord, and outside gfci, ok to final
ELE06-02077 Electrical Rough-In9/1/20069/5/20069/5/2006 8:58:30 AMACANC
Tim; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt see conf
ELE06-02077 Conference9/5/20069/5/20069/5/2006 8:58:06 AMADONE
Tim; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt talked about requirements for smoke detectors, dining , closet, make-up , when to call for ri