Inspections for the day of: Tuesday, September 5, 2006.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00137 INSP-Sprinkler Rough-in9/5/20069/5/20069/6/2006 1:00:13 PMPFAIL
Underground piping is laying in the trench but thrust blocks and bury wire is missing. The piping does not meet the 4'-6" minimum bury depth. I went over this with the fire sprinkler and general conractor. They stated that the landscaping would be raised to meet code.
FIR05-00536 INSP-Sprinkler Rough-in9/5/20069/5/20069/5/2006 4:53:04 PMPPASS
The pendant sprinkler piping in the corridor in the basement that connects the mechanical room to the south tower is ok to cover. The third floor east stair tower piping above the ceiling is ok to cover.
FIR06-00388 FIR-Aging Inspection9/5/20069/5/20069/5/2006 3:31:05 PM NR
The fire alarm contrator is waiting for additional sprinkler items to be finished.
MIS06-00227 FIR-Final9/5/20069/5/20069/5/2006 1:51:00 PMPFAIL
Provide emergency lights and exit signs as shown on the plans, provide approved hardware on the rear door and provide the missing covers on the electrical outlets.
MIS06-00223 FIR-Final9/1/20069/5/20069/5/2006 1:25:03 PMPPART
A temporary occupancy was given until the fire extinguisher is provided with a current inspection tag, the exit signs and emergency lights are repaired, remove the dead bolts from the rear exit, provide automatic flush bolts for the inactive leaf of the main exit and provide sprinkler coverage at the rear door. The manual bolt at the rear exit could remain, exception for storage areas, as long as the exit signs are removed since only one exit is required which is at the front of the tenant.
FIR06-00391 INSP-Final Inspection9/1/20069/5/20069/5/2006 12:29:37 PMAFAIL
Items passed are phone lines 1 and 2, smoke detector and pull station. Tamper switches failed. No other sprinkler items tested.
BLD03-00590 FIRE-Final Inspection9/1/20069/5/20069/5/2006 11:53:37 AMAFAIL
Fire extinguishers need tagged and installed as discussed and the door hardware needs to be approved type as discussed. Landing is missing from the west exit.
FIR06-00168 INSP-Supply line flush9/1/20069/5/20069/5/2006 11:52:34 AMAPASS
Underground flush passed.