ELE06-03975
| Final | 9/5/2007 | 9/5/2007 | 9/5/2007 5:02:23 PM | P | FAIL |
|
|
Allen; Phone #: ###-#### Internet Inspection Request from: Hattie James called no romex allowed for commercial jobs
|
ELE07-01434
| Final | 9/5/2007 | 9/5/2007 | 9/5/2007 4:55:48 PM | P | FAIL |
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Hattie James met owner needs gfci all garage recepts hole in fixtures to access box, use only sq D breakers, terminat GEC at neutral bus , install bond screw, install all covers, u/g ok for cover
|
ELE07-03044
| Permanent Service | 9/5/2007 | 9/5/2007 | 9/5/2007 4:32:58 PM | P | FAIL |
|
|
Olga; Phone #: ###-#### Internet Inspection Request from: Hattie James; call for access called corr p/s shall meet all requirements of 2005 NEC no exception, clearences, grding, bonding
|
ELE07-02532
| Electrical Rough-In | 9/5/2007 | 9/5/2007 | 9/5/2007 3:59:05 PM | P | FAIL |
|
|
Scott; Phone #: ###-#### Internet Inspection Request from: Hattie James corr, met owner 110.3(B) needs main breaker at garage panel per manufacture, 300.4 nail plates and 11/4" use listed conn or plastic conn for GEC, 300.14 free length grds cuts too short BCC no violations retained hot tub, told owner if corrections not made or more created his permit will be voided
|
ELE07-02532
| Electrical Rough-In | 9/5/2007 | 9/5/2007 | 9/5/2007 3:55:04 PM | P | PART |
|
|
Scott; Phone #: ###-#### Internet Inspection Request from: Hattie James electrode and u/g ok only
|
ELE07-02346
| Permanent Service | 9/4/2007 | 9/5/2007 | 9/5/2007 2:21:58 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 9/4/2007 at 4:56:24 PM. Contact: ###-####. p/s u/g new ok
|
ELE07-03080
| Electrical Rough-In | 9/4/2007 | 9/5/2007 | 9/5/2007 2:04:57 PM | P | FAIL |
|
|
CHRIS Phone #: ###-#### 210.11(C)(2)&(3) needs laundry circuit, outside outlet not allowed on bath circuit, 300.4(A)(1) nail plates inside outside edges, 314.16 box fill, 314.20 outside boxes not flush, 110.3(B) use manufactures breakers only, BCC no violations retained wiring of addition shall meet NEC for new dwelling 220 shall provide service calcs called corr do not cover posted also reinspection fee due COW
|
ELE07-03092
| Rough-In Permanent Service | 9/5/2007 | 9/5/2007 | 9/5/2007 12:48:47 PM | P | PASS |
|
|
We also ran a circuit for microwave above range and we need inspection of ground wire to be encased in concrete Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman r/i new addition and electrode ok, p/s u/g rec. ok
|
ELE07-01308
| Electrical Rough-In | 9/4/2007 | 9/5/2007 | 9/5/2007 10:54:46 AM | A | PART |
|
|
Rough-in inspection for tenant space #105. Electrician-Brian ###-####. Thank you. Phone #: ###-#### Internet Inspection Request from: Carla Ward ok walls ok also 5 added recepts wall between tennant spaces and warehouse
|
ELE07-02833
| Electrical Rough-In | 9/4/2007 | 9/5/2007 | 9/5/2007 10:14:45 AM | A | PART |
|
|
front soffit; Brandon; Phone #: ###-#### Internet Inspection Request from: Hattie James soffit ceiling ok
|
ELE07-02838
| Electrical Rough-In | 9/4/2007 | 9/5/2007 | 9/5/2007 9:40:55 AM | A | PASS |
|
|
chris - cover for ceiling tiles Phone #: ###-#### ok
|
ELE07-02951
| Final | 9/4/2007 | 9/5/2007 | 9/5/2007 9:14:02 AM | A | PASS |
|
|
reinspection of sewer pump - spoke with owner dogs will be gone during the morning. Phone #: ###-#### Internet Inspection Request from: Celinda Winters ok
|
ELE06-03975
| Final | 9/4/2007 | 9/5/2007 | 9/5/2007 8:48:46 AM | A | FAIL |
|
|
Allen; Phone #: ###-#### Internet Inspection Request from: Hattie James needs switch and light for building also conn for GEC called
|
ELE07-02378
| Final | 9/4/2007 | 9/5/2007 | 9/5/2007 8:23:45 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 9/4/2007 at 4:57:33 PM. Contact: ###-####. not ready no access
|