Inspections for the day of: Wednesday, September 5, 2007.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-03975 Final9/5/20079/5/20079/5/2007 5:02:23 PMPFAIL
Allen; Phone #: ###-#### Internet Inspection Request from: Hattie James called no romex allowed for commercial jobs
ELE07-01434 Final9/5/20079/5/20079/5/2007 4:55:48 PMPFAIL
Mike; Phone #: ###-#### Internet Inspection Request from: Hattie James met owner needs gfci all garage recepts hole in fixtures to access box, use only sq D breakers, terminat GEC at neutral bus , install bond screw, install all covers, u/g ok for cover
ELE07-03044 Permanent Service9/5/20079/5/20079/5/2007 4:32:58 PMPFAIL
Olga; Phone #: ###-#### Internet Inspection Request from: Hattie James; call for access called corr p/s shall meet all requirements of 2005 NEC no exception, clearences, grding, bonding
ELE07-02532 Electrical Rough-In9/5/20079/5/20079/5/2007 3:59:05 PMPFAIL
Scott; Phone #: ###-#### Internet Inspection Request from: Hattie James
corr, met owner 110.3(B) needs main breaker at garage panel per manufacture, 300.4 nail plates and 11/4" use listed conn or plastic conn for GEC, 300.14 free length grds cuts too short BCC no violations retained hot tub, told owner if corrections not made or more created his permit will be voided
ELE07-02532 Electrical Rough-In9/5/20079/5/20079/5/2007 3:55:04 PMPPART
Scott; Phone #: ###-#### Internet Inspection Request from: Hattie James electrode and u/g ok only
ELE07-02346 Permanent Service9/4/20079/5/20079/5/2007 2:21:58 PMPPASS
Scheduled by a contractor via Hello! on 9/4/2007 at 4:56:24 PM. Contact: ###-####. p/s u/g new ok
ELE07-03080 Electrical Rough-In9/4/20079/5/20079/5/2007 2:04:57 PMPFAIL
CHRIS Phone #: ###-#### 210.11(C)(2)&(3) needs laundry circuit, outside outlet not allowed on bath circuit, 300.4(A)(1) nail plates inside outside edges, 314.16 box fill, 314.20 outside boxes not flush, 110.3(B) use manufactures breakers only, BCC no violations retained wiring of addition shall meet NEC for new dwelling 220 shall provide service calcs called corr do not cover posted also reinspection fee due
COW
ELE07-03092 Rough-In Permanent Service9/5/20079/5/20079/5/2007 12:48:47 PMPPASS
We also ran a circuit for microwave above range and we need inspection of ground wire to be encased in concrete Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman r/i new addition and electrode ok, p/s u/g rec. ok
ELE07-01308 Electrical Rough-In9/4/20079/5/20079/5/2007 10:54:46 AMAPART
Rough-in inspection for tenant space #105. Electrician-Brian ###-####. Thank you. Phone #: ###-#### Internet Inspection Request from: Carla Ward ok walls ok also 5 added recepts wall between tennant spaces and warehouse
ELE07-02833 Electrical Rough-In9/4/20079/5/20079/5/2007 10:14:45 AMAPART
front soffit; Brandon; Phone #: ###-#### Internet Inspection Request from: Hattie James soffit ceiling ok
ELE07-02838 Electrical Rough-In9/4/20079/5/20079/5/2007 9:40:55 AMAPASS
chris - cover for ceiling tiles Phone #: ###-#### ok
ELE07-02951 Final9/4/20079/5/20079/5/2007 9:14:02 AMAPASS
reinspection of sewer pump - spoke with owner dogs will be gone during the morning. Phone #: ###-#### Internet Inspection Request from: Celinda Winters
ok
ELE06-03975 Final9/4/20079/5/20079/5/2007 8:48:46 AMAFAIL
Allen; Phone #: ###-#### Internet Inspection Request from: Hattie James
needs switch and light for building also conn for GEC called
ELE07-02378 Final9/4/20079/5/20079/5/2007 8:23:45 AMAFAIL
Scheduled by a contractor via Hello! on 9/4/2007 at 4:57:33 PM. Contact: ###-####. not ready no access