Inspections for the day of: Wednesday, September 5, 2007.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-03091 Permanent Service9/5/20079/5/20079/5/2007 3:44:24 PMPFAIL
called, said we can do first thing in am, nec items left corr notice, 250.92(B) shall use ground bushings around concentric in service panel, 110.14(A) terminals shall be tight at ground rods,BCC shall provide access to panel, need someone there, need to check for water pipe ground
ELE07-03085 Rough-In Permanent Service9/5/20079/5/20079/5/2007 3:33:31 PMPFAIL
Tom; Phone #: ###-#### Internet Inspection Request from: Hattie James called ,NEC 110.26(a) work space shall be provided about equipment- no low voltage below panel, 312.5 shall provide abrasion protection for all conductors entering enclosures, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 314.20 boxes shall be flush with finished surface in walls of combustible materials, 210.52(A)(2) shall provide recpts in 2' walls, 334.30 flat nm cable shall not be stapled on edge, 314.17(C) nm cable shall be stapled within 8" of box, BCC all underground shall be inspected before cover, address shall be posted
ELE07-03084 Rough-In Permanent Service9/5/20079/5/20079/5/2007 2:37:10 PMPCANC
Tom; Phone #: ###-#### Internet Inspection Request from: Hattie James see r/i and p/s
ELE07-03083 Electrical Rough-In9/5/20079/5/20079/5/2007 2:36:21 PMPFAIL
Tom; Phone #: ###-#### Internet Inspection Request from: Hattie James called nec 312.5 all conductors entering enclosures shall have abrasion protection, 314.20 boxes shall be flush with finished surface in walls of combustible material, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from face of framing members, 210.52(A)(1)&(2) 2' walls shall have recpt installed, recpt shall be within 6' of entry,210.53 (A) recpt shall be installed at rear of dwelling, BCC all u/g shall be inspected before cover, address shall be posted
ELE07-03084 Electrical Rough-In9/5/20079/5/20079/5/2007 2:35:06 PMPFAIL
Tom; Phone #: ###-#### Internet Inspection Request from: Hattie James called, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 210.53(A) recpt shall be at rear of dwelling, 210.52(A)(2) 2' walls shall have recpts installed, 312.5 shall provide abrasion protection for all conductors entering enclosures, BCC all u/g shall be inspected before cover, address shall be posted
ELE07-03084 Permanent Service9/5/20079/5/20079/5/2007 2:30:10 PMPPASS
Tom; Phone #: ###-#### Internet Inspection Request from: Hattie James p/s u/g n ok
ELE07-03083 Rough-In Permanent Service9/5/20079/5/20079/5/2007 2:26:49 PMPCANC
Tom; Phone #: ###-#### Internet Inspection Request from: Hattie James see ri and p/s
ELE07-03083 Permanent Service9/5/20079/5/20079/5/2007 2:20:57 PMPPASS
Tom; Phone #: ###-#### Internet Inspection Request from: Hattie James p/s u/g n ok
ELE07-03061 Temporary Service9/5/20079/5/20079/5/2007 1:11:25 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot t/s o/h n ok
ELE07-02501 Final9/5/20079/5/20079/5/2007 12:56:54 PMAPART
Temporary Occupancy Phone #: ###-#### Internet Inspection Request from: Dan Surerus signed t/o card need to see installed equipment for to final, corrections made
ELE07-03064 Permanent Service9/4/20079/5/20079/5/2007 12:32:28 PMPPASS
INSPECTION ON SERVICE UPGRADE CONTACT JACK Phone #: ###-#### Internet Inspection Request from: Emmet Bushman p/s u/g rec ok
ELE07-02589 Final9/4/20079/5/20079/5/2007 10:56:41 AMAPASS
Owners to be home. Scheduled by Heather w/Doherty. Phone #: ###-#### Internet Inspection Request from: Heather Packer called , ok to final
ELE07-02299 Final9/4/20079/5/20079/5/2007 10:28:10 AMAPASS
Terry; Phone #: ###-#### Internet Inspection Request from: Hattie James corrections made, ok to final, signed struct card only
ELE07-00799 Final9/4/20079/5/20079/5/2007 10:06:26 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok to final
ELE07-02093 Final9/4/20079/5/20079/5/2007 9:33:59 AMAPART
This is for partial final - please Mike w/Doherty @ ###-#### for an description and to answer any questions. Scheduled by Heather w/Doherty Phone #: ###-#### Internet Inspection Request from: Heather Packer ok to occupy 1st 1/2 east part, called contr, did not sign card, 2 gfci covers missing
ELE07-02514 Electrical Rough-In9/4/20079/5/20079/5/2007 8:56:17 AMAPASS
Scheduled by a contractor via Hello! on 9/4/2007 at 3:02:11 PM. Contact: ###-####. ric ok, walls and ceilings
ELE07-01168 Electrical Rough-In9/4/20079/5/20079/5/2007 8:52:05 AMAPASS
Scheduled by a contractor via Hello! on 9/4/2007 at 3:00:57 PM. Contact: ###-####. ric ok, walls and ceilings
ELE07-01170 Electrical Rough-In9/4/20079/5/20079/5/2007 8:51:09 AMAPASS
Scheduled by a contractor via Hello! on 9/4/2007 at 3:03:26 PM. Contact: ###-####. ric ok, walls and ceilings
ELE07-03071 Permanent Service9/4/20079/5/20079/5/2007 8:33:01 AMPCANC
As late in the afternoon as possible please, this is a service change. Phone #: ###-#### Internet Inspection Request from: Tracy Robertson Inspection cancelled from web by: Tracy Robertson