ELE07-03091
| Permanent Service | 9/5/2007 | 9/5/2007 | 9/5/2007 3:44:24 PM | P | FAIL |
|
|
called, said we can do first thing in am, nec items left corr notice, 250.92(B) shall use ground bushings around concentric in service panel, 110.14(A) terminals shall be tight at ground rods,BCC shall provide access to panel, need someone there, need to check for water pipe ground
|
ELE07-03085
| Rough-In Permanent Service | 9/5/2007 | 9/5/2007 | 9/5/2007 3:33:31 PM | P | FAIL |
|
|
Tom; Phone #: ###-#### Internet Inspection Request from: Hattie James called ,NEC 110.26(a) work space shall be provided about equipment- no low voltage below panel, 312.5 shall provide abrasion protection for all conductors entering enclosures, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 314.20 boxes shall be flush with finished surface in walls of combustible materials, 210.52(A)(2) shall provide recpts in 2' walls, 334.30 flat nm cable shall not be stapled on edge, 314.17(C) nm cable shall be stapled within 8" of box, BCC all underground shall be inspected before cover, address shall be posted
|
ELE07-03084
| Rough-In Permanent Service | 9/5/2007 | 9/5/2007 | 9/5/2007 2:37:10 PM | P | CANC |
|
|
Tom; Phone #: ###-#### Internet Inspection Request from: Hattie James see r/i and p/s
|
ELE07-03083
| Electrical Rough-In | 9/5/2007 | 9/5/2007 | 9/5/2007 2:36:21 PM | P | FAIL |
|
|
Tom; Phone #: ###-#### Internet Inspection Request from: Hattie James called nec 312.5 all conductors entering enclosures shall have abrasion protection, 314.20 boxes shall be flush with finished surface in walls of combustible material, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from face of framing members, 210.52(A)(1)&(2) 2' walls shall have recpt installed, recpt shall be within 6' of entry,210.53 (A) recpt shall be installed at rear of dwelling, BCC all u/g shall be inspected before cover, address shall be posted
|
ELE07-03084
| Electrical Rough-In | 9/5/2007 | 9/5/2007 | 9/5/2007 2:35:06 PM | P | FAIL |
|
|
Tom; Phone #: ###-#### Internet Inspection Request from: Hattie James called, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 210.53(A) recpt shall be at rear of dwelling, 210.52(A)(2) 2' walls shall have recpts installed, 312.5 shall provide abrasion protection for all conductors entering enclosures, BCC all u/g shall be inspected before cover, address shall be posted
|
ELE07-03084
| Permanent Service | 9/5/2007 | 9/5/2007 | 9/5/2007 2:30:10 PM | P | PASS |
|
|
Tom; Phone #: ###-#### Internet Inspection Request from: Hattie James p/s u/g n ok
|
ELE07-03083
| Rough-In Permanent Service | 9/5/2007 | 9/5/2007 | 9/5/2007 2:26:49 PM | P | CANC |
|
|
Tom; Phone #: ###-#### Internet Inspection Request from: Hattie James see ri and p/s
|
ELE07-03083
| Permanent Service | 9/5/2007 | 9/5/2007 | 9/5/2007 2:20:57 PM | P | PASS |
|
|
Tom; Phone #: ###-#### Internet Inspection Request from: Hattie James p/s u/g n ok
|
ELE07-03061
| Temporary Service | 9/5/2007 | 9/5/2007 | 9/5/2007 1:11:25 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot t/s o/h n ok
|
ELE07-02501
| Final | 9/5/2007 | 9/5/2007 | 9/5/2007 12:56:54 PM | A | PART |
|
|
Temporary Occupancy Phone #: ###-#### Internet Inspection Request from: Dan Surerus signed t/o card need to see installed equipment for to final, corrections made
|
ELE07-03064
| Permanent Service | 9/4/2007 | 9/5/2007 | 9/5/2007 12:32:28 PM | P | PASS |
|
|
INSPECTION ON SERVICE UPGRADE CONTACT JACK Phone #: ###-#### Internet Inspection Request from: Emmet Bushman p/s u/g rec ok
|
ELE07-02589
| Final | 9/4/2007 | 9/5/2007 | 9/5/2007 10:56:41 AM | A | PASS |
|
|
Owners to be home. Scheduled by Heather w/Doherty. Phone #: ###-#### Internet Inspection Request from: Heather Packer called , ok to final
|
ELE07-02299
| Final | 9/4/2007 | 9/5/2007 | 9/5/2007 10:28:10 AM | A | PASS |
|
|
Terry; Phone #: ###-#### Internet Inspection Request from: Hattie James corrections made, ok to final, signed struct card only
|
ELE07-00799
| Final | 9/4/2007 | 9/5/2007 | 9/5/2007 10:06:26 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok to final
|
ELE07-02093
| Final | 9/4/2007 | 9/5/2007 | 9/5/2007 9:33:59 AM | A | PART |
|
|
This is for partial final - please Mike w/Doherty @ ###-#### for an description and to answer any questions. Scheduled by Heather w/Doherty Phone #: ###-#### Internet Inspection Request from: Heather Packer ok to occupy 1st 1/2 east part, called contr, did not sign card, 2 gfci covers missing
|
ELE07-02514
| Electrical Rough-In | 9/4/2007 | 9/5/2007 | 9/5/2007 8:56:17 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 9/4/2007 at 3:02:11 PM. Contact: ###-####. ric ok, walls and ceilings
|
ELE07-01168
| Electrical Rough-In | 9/4/2007 | 9/5/2007 | 9/5/2007 8:52:05 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 9/4/2007 at 3:00:57 PM. Contact: ###-####. ric ok, walls and ceilings
|
ELE07-01170
| Electrical Rough-In | 9/4/2007 | 9/5/2007 | 9/5/2007 8:51:09 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 9/4/2007 at 3:03:26 PM. Contact: ###-####. ric ok, walls and ceilings
|
ELE07-03071
| Permanent Service | 9/4/2007 | 9/5/2007 | 9/5/2007 8:33:01 AM | P | CANC |
|
|
As late in the afternoon as possible please, this is a service change. Phone #: ###-#### Internet Inspection Request from: Tracy Robertson Inspection cancelled from web by: Tracy Robertson
|