ELE08-02458
| Electrical Rough-In | 9/5/2008 | 9/5/2008 | 9/5/2008 4:03:07 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 9/5/2008 at 9:41:18 AM. Contact: ###-####. corrections made, ric ok
|
ESC08-00673
| General Inspection | 9/5/2008 | 9/5/2008 | 9/5/2008 3:11:18 PM | P | PART |
|
|
looked ok
|
ESC06-01310
| General Inspection | 9/5/2008 | 9/5/2008 | 9/5/2008 2:41:59 PM | P | PART |
|
|
looked ok
|
ESC08-00673
| General Inspection | 9/5/2008 | 9/5/2008 | 9/5/2008 2:17:47 PM | A | PART |
|
|
looked ok
|
ELE08-00828
| Electrical Rough-In | 9/4/2008 | 9/5/2008 | 9/5/2008 1:47:07 PM | P | PART |
|
|
MORGAN Phone #: ###-#### Internet Inspection Request from: Sean DeLacy east building north 1/2 slab only ok to pour
|
ELE08-01312
| Final | 9/5/2008 | 9/5/2008 | 9/5/2008 12:38:29 PM | P | NH |
|
|
Call homeowner ahead of time to gain access to home. ###-#### Call me with any questions about inspection ###-#### Phone #: ###-#### Internet Inspection Request from: Cevyn Recla called owner, set up time to meet, he didn't show up, called contractor, left sticker, fee due, no esc this project
|
ELE07-03307
| Conference | 9/4/2008 | 9/5/2008 | 9/5/2008 10:22:51 AM | A | DONE |
|
|
Contact: Phil Bassick, would like to meet at job site about 10:30 if possible. please call before going Phone #: ###-#### Internet Inspection Request from: Deb Gooden met contractor to get copy of one-line to review service for condos
|
ELE08-02454
| Electrical Rough-In | 9/4/2008 | 9/5/2008 | 9/5/2008 10:09:04 AM | A | PASS |
|
|
don Phone #: ###-#### ric ok, no esc this project
|
ELE08-02458
| Electrical Rough-In | 9/4/2008 | 9/5/2008 | 9/5/2008 9:37:28 AM | A | FAIL |
|
|
john Phone #: ###-#### called, left correction notice, NEC 300.14 at least 6" free conductor shall be left at each outlet point, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 334.30 flat nm cable shall not be stapled on edge
|
ELE08-02211
| Temporary Service | 9/4/2008 | 9/5/2008 | 9/5/2008 8:59:37 AM | A | NR |
|
|
Dale Phone #: ###-#### met electrician, needs to backfill and provide distribution board, protect u/g conduit, strap conduit, change ground abrasion protection, will fix and call when ready, no esc this project
|
ELE08-02009
| Electrical Rough-In | 9/4/2008 | 9/5/2008 | 9/5/2008 8:03:52 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Bryan McLaughlin ok to cover ceilings, no esc this project
|