Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-02458 Electrical Rough-In9/5/20089/5/20089/5/2008 4:03:07 PMPPASS
Scheduled by a contractor via Hello! on 9/5/2008 at 9:41:18 AM. Contact: ###-####. corrections made, ric ok
ESC08-00673 General Inspection9/5/20089/5/20089/5/2008 3:11:18 PMPPART
looked ok
ESC06-01310 General Inspection9/5/20089/5/20089/5/2008 2:41:59 PMPPART
looked ok
ESC08-00673 General Inspection9/5/20089/5/20089/5/2008 2:17:47 PMAPART
looked ok
ELE08-00828 Electrical Rough-In9/4/20089/5/20089/5/2008 1:47:07 PMPPART
MORGAN Phone #: ###-#### Internet Inspection Request from: Sean DeLacy east building north 1/2 slab only ok to pour
ELE08-01312 Final9/5/20089/5/20089/5/2008 12:38:29 PMPNH
Call homeowner ahead of time to gain access to home. ###-####
Call me with any questions about inspection
###-#### Phone #: ###-#### Internet Inspection Request from: Cevyn Recla called owner, set up time to meet, he didn't show up, called contractor, left sticker, fee due, no esc this project
ELE07-03307 Conference9/4/20089/5/20089/5/2008 10:22:51 AMADONE
Contact: Phil Bassick, would like to meet at job site about 10:30 if possible. please call before going Phone #: ###-#### Internet Inspection Request from: Deb Gooden met contractor to get copy of one-line to review service for condos
ELE08-02454 Electrical Rough-In9/4/20089/5/20089/5/2008 10:09:04 AMAPASS
don Phone #: ###-#### ric ok, no esc this project
ELE08-02458 Electrical Rough-In9/4/20089/5/20089/5/2008 9:37:28 AMAFAIL
john Phone #: ###-#### called, left correction notice, NEC 300.14 at least 6" free conductor shall be left at each outlet point, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 334.30 flat nm cable shall not be stapled on edge
ELE08-02211 Temporary Service9/4/20089/5/20089/5/2008 8:59:37 AMANR
Dale Phone #: ###-#### met electrician, needs to backfill and provide distribution board, protect u/g conduit, strap conduit, change ground abrasion protection, will fix and call when ready, no esc this project
ELE08-02009 Electrical Rough-In9/4/20089/5/20089/5/2008 8:03:52 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Bryan McLaughlin ok to cover ceilings, no esc this project