BLD19-03279
| FIRE-Final Inspection | 9/3/2019 | 9/5/2019 | 9/6/2019 6:21:37 AM | P | CANC |
|
|
Rescheduled for tomorrow. call for access- Charlie Phone #: ###-####
|
NAF19-00100
| INSP-Sprinkler Rough-in | 9/5/2019 | 9/5/2019 | 9/5/2019 2:32:34 PM | P | PASS |
|
|
Rough-in passed. Piping is ok for cover.
Jon Beazer is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
NAF19-00085
| INSP-Sprinkler Rough-in/Hydro | 9/4/2019 | 9/5/2019 | 9/5/2019 2:30:01 PM | P | PART |
|
|
Plan mods need to be submitted showing the actual pipe routing, fittings and additional supply to second floor. Need tenting inspection when complete. Rough-in appears ok, just need the plans to match. Also the short piece at the top of the riser has been installed 3/4" instead of 1". No piping to be covered yet.
Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD18-03121
| FIRE-Final Inspection | 9/5/2019 | 9/5/2019 | 9/5/2019 1:22:00 PM | P | PART |
|
|
The six apartments, 1st through 3rd floors at the very north end of this building have the life safety passed. The FDC needs the required clearance as discussed prior to a final inspection. Matt Phone #: ###-####
|
FIR19-00309
| INSP-Final Inspection | 9/4/2019 | 9/5/2019 | 9/5/2019 12:41:07 PM | A | PART |
|
|
The fire sprinkler work in the six north end apartments is complete. 1st - 3rd floors. The fire alarm interconnect is complete. FDC nees relocated from the air conditioner condenser.
Gabe Garduno is the contact for this final inspection. Thank you for your help. Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD19-03360
| FIRE-Final Inspection | 9/4/2019 | 9/5/2019 | 9/5/2019 10:35:00 AM | A | PASS |
|
|
Life safety passed. Songa Phone #: ###-####
|
BLD19-03309
| FIRE-Final Inspection | 9/4/2019 | 9/5/2019 | 9/5/2019 9:24:51 AM | A | FAIL |
|
|
Provide annual inspection for the fire extinguisher, remove thumbturn dead bolt at main exit (keyed is ok) and provide sticker, remove round knob at main exit (single action lever type ok). Before 11 // Merinda Phone #: ###-####
|
FIR18-00697
| INSP-Final Inspection | 9/4/2019 | 9/5/2019 | 9/5/2019 8:53:27 AM | A | PASS |
|
|
Permit finaled
|
FIR19-00203
| INSP-Final Inspection | 9/4/2019 | 9/5/2019 | 9/5/2019 8:25:26 AM | A | PASS |
|
|
Permit finaled. Eric Phone #: ###-####
|
BLD19-00228
| FIRE-Final Inspection | 9/4/2019 | 9/5/2019 | 9/5/2019 8:24:53 AM | A | PART |
|
|
A temporary for life safety is ok per boise fire until the upgrade agreement for the fire alarm system has been finalized. Phone #: ###-#### Inspection requested via web by Russell Valline
|