Inspections for the day of: Wednesday, September 6, 2006.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-03323 Final9/6/20069/6/20069/6/2006 1:55:37 PMPPASS
inspect temp power pole.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH
ELE06-03323 Temporary Service9/6/20069/6/20069/6/2006 1:55:25 PMPPASS
inspect temp power pole.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH t/s o/h new ok
ELE06-02666 Final9/6/20069/6/20069/6/2006 1:40:32 PMPPASS
neal - reinsp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
ok
ELE06-02766 Final9/6/20069/6/20069/6/2006 1:14:38 PMPPASS
JEAN; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
ELE06-02629 Electrical Rough-In9/6/20069/6/20069/6/2006 12:50:36 PMPPASS
john; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles r/i ok
ELE06-02806 Final9/6/20069/6/20069/6/2006 12:00:00 PMPPASS
charles; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
ELE06-03314 Temporary Service9/6/20069/6/20069/6/2006 10:20:30 AMPPASS
marvin; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
t/s u/g new ok
ELE06-02766 Final9/5/20069/6/20069/6/2006 10:04:15 AMANR
gene-- ###-#### cell
ELE03-00785 DOC - Permit Finaled9/6/20069/6/20069/6/2006 9:10:05 AMAPASS
ELE05-00649 Final9/6/20069/6/20069/6/2006 9:09:07 AMAPASS
ELE04-03088 Electrical Rough-In9/5/20069/6/20069/6/2006 9:04:46 AMAFAIL
loren; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
corr. met owner, 300.4 nail plates and 11/4", 210.52(A)&(E) needs outlet bed rm wall behind door and outside front gfci outlet, 334.15 protect romex expose on post in basement note afci for bed circuits, install smoke detector system, complete all makeup