Inspections for the day of: Wednesday, September 6, 2006.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMike Jordan
TitleBLD-COM/RES INSPECTOR
Phone #794-9473
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-03025 BLD-Framing/Rough-in9/5/20069/6/20069/6/2006 4:46:51 PMPFAIL
Scheduled by a contractor via Hello! on 9/5/2006 at 10:52:27 AM. Contact: ###-####. Needs to complete the fire caulking at the 1st floor corridor lids. not ok to cover.
BLD05-02379 BLD-Final9/6/20069/6/20069/6/2006 3:17:31 PMPPART
Ok for temp occ. Needs final Aff. letter from special insp. lab. Also needs to get elec. and public works finaled.
BLD06-00660 BLD-Foundation9/6/20069/6/20069/6/2006 2:32:03 PMPPART
wip. perimeter stemwall. Needs to tie verts for cmu walls.
BLD06-00595 BLD-Final9/6/20069/6/20069/6/2006 1:48:26 PMPPASS
dan; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
BLD06-00595 DOC - Permit Finaled9/6/20069/6/20069/6/2006 1:48:12 PMPPASS
Smoke detectors have been installed.
MIS06-00199 BLD-Final9/6/20069/6/20069/6/2006 1:25:31 PMPPART
Sylvia; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt. Block and tie ok. Needs to install skirting, stairs at backdoor, and have other trades finaled.
BLD06-01990 BLD-Footing9/5/20069/6/20069/6/2006 1:01:47 PMPCANC
matt; Phone #: ###-#### Internet Inspection Request from: Cathy Chile. Cancelled by contractor.
BLD06-01635 BLD-Aging Inspection9/6/20069/6/20069/6/2006 11:41:47 AM NR
BLD04-02214 BLD-Aging Inspection9/6/20069/6/20069/6/2006 11:41:19 AM CANC
BLD06-01637 BLD-Aging Inspection9/6/20069/6/20069/6/2006 11:40:47 AM CANC
BLD06-00007 BLD-Wall cover9/5/20069/6/20069/6/2006 10:59:55 AMAPASS
###-#### - kent Note: wall framing. 2nd floor to top of wall exterior steel stud framing. Needs to install rock wall for fireblocking at floor ceiling lines.
BLD06-01978 BLD-Energy code compliance9/5/20069/6/20069/6/2006 9:27:37 AMAPASS
odie; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
BLD06-02396 BLD-Footing9/5/20069/6/20069/6/2006 9:08:57 AMAPART
jesse; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley. Notified conc. contractor to repair reinforcement so that their is 3" clearance and to clean out bottom of footing.