Inspections for the day of: Thursday, September 6, 2007.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00525 INSP-Final Inspection9/5/20079/6/20079/10/2007 1:22:49 PMADEFR
See inspection comments on 9/10.
FIR07-00441 INSP-Alarm Testing9/5/20079/6/20079/7/2007 11:56:22 AMAPART
Reinspection for the first floor office area defficiencies, see approved plan set for locations tested today and items in need of correction including blocked strobe notification, incorrect descriptor at an electrical room smoke, SD at an electrical closet, noted ECS room is now staffed with trained personel.
FIR07-00680 INSP-Final Inspection9/6/20079/6/20079/7/2007 11:50:46 AMPNR
Inspection rescheduled.
BLD07-00293 FIRE-Final Inspection9/6/20079/6/20079/6/2007 3:07:36 PMPPASS
Corrections are complete, fire life safety finaled.
BLD07-00959 FIRE-Final Inspection9/4/20079/6/20079/6/2007 3:05:29 PMPPASS
Two PFE's installed while on site, corresponding suite address numbers also provided while on site, fire life safety inspection passed.
FIR07-00514 INSP-Final Inspection9/6/20079/6/20079/6/2007 3:02:52 PMPPASS
Fire sprinkler final inspection passed, permit finaled.
FIR07-00725 INSP-Final Inspection9/6/20079/6/20079/6/2007 3:01:48 PMPPASS
Fire alarm system modification tested satisfactory. Instructed the building manager to remove the chest freezer located in the fire command center ASAP.
FIR07-00185 FIR-Aging Inspection9/6/20079/6/20079/6/2007 1:14:14 PM DEFR
FIR07-00501 INSP-Sprinkler Rough-in/Hydro9/5/20079/6/20079/6/2007 1:12:50 PMAPART
OH hydrostatic test passed. No occupancy is allowed prior to the issuance of a certificate of occupancy for the building per conditon of the issued project permits.
FIR07-00502 INSP-Sprinkler Rough-in9/5/20079/6/20079/6/2007 11:14:22 AMAPART
OH rough-in is approved except as noted or not yet complete-see annotations on stamped plan set including seismic clearance at a 4" riser, overspaced heads due to HVAC, missing head at the janitors room, SW at the overhead doors are not installed at this time.
FIR07-00725 INSP-Final Inspection9/6/20079/6/20079/6/2007 10:22:54 AMADONE
Duplicate inspection request.
BLD07-00792 FIRE-Final Inspection9/4/20079/6/20079/6/2007 10:21:38 AMAPART
Fire life safety for the area indicated as phase one is acceptable.
FIR07-00698 INSP-Final Inspection9/5/20079/6/20079/6/2007 10:20:24 AMAPART
See approved plans for areas inspected today noted as "phase 1" including new horns and two in duct detectors, verified as-builts for field modifications and address changes.