Inspections for the day of: Thursday, September 6, 2007.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-00427 FIRE-Final Inspection9/6/20079/6/20079/6/2007 5:20:10 PMPCANC
Overbooked
BLD07-01530 FIRE-Final Inspection9/6/20079/6/20079/6/2007 5:13:25 PMPFAIL
Need the doors and hardware installed. Also need the duct smoke detectors with the remote annunciators as per the approved plans. These will need to be tested when installed. All other items are ok.
FIR06-00011 INSP-Alarm Testing9/5/20079/6/20079/6/2007 4:57:35 PMPDONE
See mike timmermans notes for items tested.
FIR07-00351 INSP-Sprinkler Rough-in/Hydro9/5/20079/6/20079/6/2007 4:52:17 PMAPASS
The sprinkler piping above the ceiling tile is ok to cover.
FIR05-00536 INSP-Final Inspection9/5/20079/6/20079/6/2007 4:47:40 PMAFAIL
The west half of the second floor sprinkler system is ok to final when the missing head in the electrical closet is installed.
FIR06-00957 INSP-Final Inspection9/5/20079/6/20079/6/2007 11:53:47 AMAFAIL
I inspected the second floor wings D, C and B. As with the previous inspection many pendants are blocked and the electrical room is missing coverage. I stopped the inspection until all of blocked heads have been fixed.
FIR06-00956 INSP-Final Inspection9/5/20079/6/20079/6/2007 11:48:26 AMAFAIL
I inspected the second floor wings D, C and B. As with the previous inspection many pendants are blocked and the electrical room is missing coverage. I stopped the inspection until all of blocked heads have been fixed.
FIR06-00958 INSP-Final Inspection9/5/20079/6/20079/6/2007 11:31:18 AMAFAIL
I inspected the second floor wings D, C and B. As with the previous inspection many pendants are blocked and the electrical room is missing coverage. I stopped the inspection until all of blocked heads have been fixed.
FIR07-00596 INSP-Sprinkler Rough-in9/6/20079/6/20079/6/2007 10:19:24 AMPCANC
OH Cover Inspection Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
FIR07-00596 INSP-Sprinkler Rough-in9/5/20079/6/20079/6/2007 9:10:41 AMACANC
OH Cover Inspection Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
BLD06-02674 FIRE-Final Inspection9/5/20079/6/20079/5/2007 1:57:36 PMAPASS
life safety passed