Inspections for the day of: Tuesday, September 6, 2011.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD11-01358 FIRE-Final Inspection9/6/20119/6/20119/6/2011 4:23:15 PMPPASS
Fire life safety inspection completed.
FIR11-00328 INSP-Final Inspection9/6/20119/6/20119/6/2011 4:20:20 PMPPASS
Fire sprinkler permit final approved.
BLD11-01659 FIRE-Final Inspection9/6/20119/6/20119/6/2011 4:19:00 PMPPASS
C/N items verified for completion. Fire life safety finaled.
FIR11-00228 INSP-Alarm Testing8/31/20119/6/20119/6/2011 4:17:46 PMAPART
Noted correction items include; breaker lock at the panel, signage at doors to the FACP room, remove two non-functional existing SD, post points map at the panel, relocate two MP stations to no higher than 48" AFF, add visual coverage at the copy room 1st floor, provide letter regarding elevator. Items tested today include notification throughout, all HD and MP, panel conditons, sprinkler monitoring, duct detectors, and beam detectors. Settings at two notification appliances adjusted while on site.
BLD11-01569 FIRE-Sprinkler Rough-in9/6/20119/6/20119/6/2011 4:06:29 PMAPART
Overhead fire sprinkler modifications okay for cover.
BLD10-01853 FIRE-Conference9/6/20119/6/20119/6/2011 4:05:37 PMADONE
FIR11-00355 INSP-Sprinkler Rough-in/Hydro9/6/20119/6/20119/6/2011 4:04:55 PMAPART
See approved plans for marked and dated locations inspected to date.
BLD11-01653 FIRE-Alarm Testing9/6/20119/6/20119/6/2011 2:45:42 PMAPASS
Project related fire alarm permit work passed inspection.