Inspections for the day of: Friday, September 6, 2013.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00333 INSP-Final Inspection9/6/20139/6/20139/6/2013 3:51:08 PMPPASS
Permit finaled
FIR13-00313 INSP-Final Inspection9/6/20139/6/20139/6/2013 3:48:44 PMPPASS
Permit finaled
FIR12-00698 INSP-Alarm Testing9/6/20139/6/20139/6/2013 3:43:34 PMPCANC
Call prior to going Phone #: 2089411846 >> Inspection requested via mobile web by Brian Anderson Inspection cancelled via mobile web on Friday, September 06, 2013.
FIR13-00204 INSP-Final Inspection9/5/20139/6/20139/6/2013 3:15:51 PMPFAIL
Need forward flush to final.
BLD13-01369 FIRE-Final Inspection9/6/20139/6/20139/6/2013 3:09:02 PMAFAIL
Remove the thumbturn lock at the main exit, provide canopies for the pendant sprinkler heads, remove tape from uprights in stock room. aquire a racking permit for the storage racks that exceed 8'.
BLD10-02432 FIRE-Final Inspection9/5/20139/6/20139/6/2013 1:36:16 PMPFAIL
Relocate the fire extinguisher to the Storage Room as per the approved plans and provide documentation or resubmittals that show the revised fire dept access on the east side of the building.
FIR13-00338 INSP-Sprinkler Rough-in/Hydro9/5/20139/6/20139/6/2013 11:18:26 AMPPART
There are two overspaced pendants and one that still needs to be installed. See red lines on plans.Tim is ok with coverage in the commonn stair well due to rated assembley. The extended coverage sidewall has not been installed yet. Riser has not been built. Tenting has not been done yet.
FIR13-00338 INSP-Supply line flush9/5/20139/6/20139/6/2013 11:08:23 AMAPART
Underground flush passed. Will have to be redone if the underground supply nees to be repaired.
FIR13-00338 INSP-Sprinkler Rough-in/Hydro9/5/20139/6/20139/6/2013 10:25:24 AMAFAIL
Ug hydro failed due visable pressure loss on guage.
BLD11-00519 FIRE-Final Inspection9/5/20139/6/20139/6/2013 9:37:46 AMAFAIL
Provide city approved plans, provide fire extinguishers, repaire the exit signs, provide NFPA signage on the H occupancy doors, provide signage on the FACP/Electrical room doors and it appears that notes 1 - 7 have not been addressed for the ventilation.