FIR13-00333
| INSP-Final Inspection | 9/6/2013 | 9/6/2013 | 9/6/2013 3:51:08 PM | P | PASS |
|
|
Permit finaled
|
FIR13-00313
| INSP-Final Inspection | 9/6/2013 | 9/6/2013 | 9/6/2013 3:48:44 PM | P | PASS |
|
|
Permit finaled
|
FIR12-00698
| INSP-Alarm Testing | 9/6/2013 | 9/6/2013 | 9/6/2013 3:43:34 PM | P | CANC |
|
|
Call prior to going Phone #: 2089411846 >> Inspection requested via mobile web by Brian Anderson Inspection cancelled via mobile web on Friday, September 06, 2013.
|
FIR13-00204
| INSP-Final Inspection | 9/5/2013 | 9/6/2013 | 9/6/2013 3:15:51 PM | P | FAIL |
|
|
Need forward flush to final.
|
BLD13-01369
| FIRE-Final Inspection | 9/6/2013 | 9/6/2013 | 9/6/2013 3:09:02 PM | A | FAIL |
|
|
Remove the thumbturn lock at the main exit, provide canopies for the pendant sprinkler heads, remove tape from uprights in stock room. aquire a racking permit for the storage racks that exceed 8'.
|
BLD10-02432
| FIRE-Final Inspection | 9/5/2013 | 9/6/2013 | 9/6/2013 1:36:16 PM | P | FAIL |
|
|
Relocate the fire extinguisher to the Storage Room as per the approved plans and provide documentation or resubmittals that show the revised fire dept access on the east side of the building.
|
FIR13-00338
| INSP-Sprinkler Rough-in/Hydro | 9/5/2013 | 9/6/2013 | 9/6/2013 11:18:26 AM | P | PART |
|
|
There are two overspaced pendants and one that still needs to be installed. See red lines on plans.Tim is ok with coverage in the commonn stair well due to rated assembley. The extended coverage sidewall has not been installed yet. Riser has not been built. Tenting has not been done yet.
|
FIR13-00338
| INSP-Supply line flush | 9/5/2013 | 9/6/2013 | 9/6/2013 11:08:23 AM | A | PART |
|
|
Underground flush passed. Will have to be redone if the underground supply nees to be repaired.
|
FIR13-00338
| INSP-Sprinkler Rough-in/Hydro | 9/5/2013 | 9/6/2013 | 9/6/2013 10:25:24 AM | A | FAIL |
|
|
Ug hydro failed due visable pressure loss on guage.
|
BLD11-00519
| FIRE-Final Inspection | 9/5/2013 | 9/6/2013 | 9/6/2013 9:37:46 AM | A | FAIL |
|
|
Provide city approved plans, provide fire extinguishers, repaire the exit signs, provide NFPA signage on the H occupancy doors, provide signage on the FACP/Electrical room doors and it appears that notes 1 - 7 have not been addressed for the ventilation.
|