FIR17-00307
| INSP-Final Inspection | 9/5/2017 | 9/6/2017 | 9/6/2017 2:15:54 PM | P | PASS |
|
|
Permit finaled for the scope of work.
|
BLD16-02899
| FIRE-Conference | 9/6/2017 | 9/6/2017 | 9/6/2017 2:04:34 PM | P | DONE |
|
|
Performed the rest of the life safety today. I need the project related fire alarm pemit finaled, NFPA signs for the oxygen room, provide fire dept access signage at the south entrance.
|
FIR17-00040
| INSP-Final Inspection | 9/5/2017 | 9/6/2017 | 9/6/2017 11:17:18 AM | A | FAIL |
|
|
Need the correct as-builts, map at the facp, test security doors interface, and record of completion.
|
FIR14-00701
| INSP-Final Inspection | 9/5/2017 | 9/6/2017 | 9/6/2017 11:13:52 AM | A | FAIL |
|
|
Not ready for final yet. Today we tested the additional strobe in the short corridor that was added. Hvac unit would not shut down upon activation of the smoke detector.