Inspections for the day of: Friday, September 6, 2019.
Number of inspections: 2
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-02623 Electrical Rough-In9/5/20199/6/20199/6/2019 2:49:07 PMAFAIL
Daryl Phone #: ###-#### NEC 225.32 Location. The disconnecting means shall be installed either inside or outside of the building or structure served or where the conductors pass through the building or structure.The disconnecting means shall be at a readily accessible location nearest the point of entrance of the conductors. NEC 210. 11(c) (3)(3) Bathroom Branch Circuits. In addition to the number of branch circuits required by other parts of this section, at least one 120-volt, 20-ampere branch circuit shall be provided to supply the bathroom(s) receptacle outlet(s). Such circuits shall have no other outlets.
ELE19-03338 Electrical Rough-In9/5/20199/6/20199/6/2019 10:47:58 AMAPASS
call for access/meet on site Phone #: ###-#### Inspection requested via web by steve sellers Rough-in ok cover basement family room, bedroom, walkin closet, bathroom