FIR05-00209
| INSP-Final Inspection | 8/30/2005 | 8/31/2005 | | A | |
|
|
Scheduled by a contractor via Hello! on 8/30/2005 at 4:20:18 PM. Contact: ###-####.
|
BLD05-01634
| FIRE-Final Inspection | 9/7/2005 | 9/7/2005 | 9/7/2005 3:55:33 PM | P | PASS |
|
|
Fire life safety passed inspection.
|
FIR05-00267
| INSP-Final Inspection | 9/6/2005 | 9/7/2005 | 9/7/2005 3:52:13 PM | A | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR05-00368
| INSP-Sprinkler Rough-in/Hydro | 9/6/2005 | 9/7/2005 | 9/7/2005 3:05:19 PM | A | PART |
|
|
Overhead hydrostatic test passed. Overhead rough-in missing retaining strap on one hanger which was installed while on site, one head appears to be overspaced at the east end from the exterior shell wall, will verify spacing at final.
|
FIR05-00509
| INSP-Sprinkler Rough-in | 9/6/2005 | 9/7/2005 | 9/7/2005 1:42:50 PM | A | PART |
|
|
Underground fire supply line is okay to cover.
|
FIR05-00547
| INSP-Final Inspection | 9/6/2005 | 9/7/2005 | 9/7/2005 11:19:40 AM | A | PART |
|
|
Overhead rough-in is good for cover, will final when all ceiling tile is installed.
|
MIS05-00115
| FIR-Final | 9/6/2005 | 9/7/2005 | 9/7/2005 10:38:18 AM | A | FAIL |
|
|
Remove manual flush bolts at double doors to the lobby waiting room, repair emergency light.
|
MIS05-00125
| FIR-Final | 9/6/2005 | 9/7/2005 | 9/7/2005 9:19:59 AM | A | FAIL |
|
|
Need to post max. occupant load sign, will verify correct door hardware on doors that have been removed and need re-installed.
|
BLD05-01347
| FIRE-Final Inspection | 9/1/2005 | 9/7/2005 | 9/7/2005 12:00:00 AM | A | CANC |
|
|
terry; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa Note; changing dates
|
FIR05-00494
| INSP-Final Inspection | 9/7/2005 | 9/7/2005 | 9/7/2005 12:00:00 AM | P | PART |
|
|
Final pending resubmittals for the added PIV tamper on unit A, alarm issues in this unit C are okay. A temp. occupancy was approved per Dave Hanneman.
|
FIR05-00495
| INSP-Final Inspection | 9/7/2005 | 9/7/2005 | 9/7/2005 12:00:00 AM | P | PART |
|
|
Final pending resubmittals showing added PIV tamper at unit A, alarm issues are okay in this unit B. A temp. occupancy was approved per Dave Hanneman.
|
BLD05-01345
| FIRE-Final Inspection | 9/7/2005 | 9/7/2005 | 9/7/2005 12:00:00 AM | P | PART |
|
|
A temporary occupancy was granted with Sam Rogers permission pending final of the fire alarm permit, all other life safety issues are acceptable.
|
FIR05-00443
| INSP-Final Inspection | 9/7/2005 | 9/7/2005 | 9/7/2005 12:00:00 AM | P | PASS |
|
|
Fire sprinkler finaled.
|