Inspections for the day of: Friday, September 7, 2007.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-03126 Conference9/7/20079/7/20079/10/2007 12:01:46 PMADONE
don ###-#### talked with owner yold requirerments and if ? call me
ELE07-02493 Final9/7/20079/7/20079/7/2007 2:41:56 PMPPASS
chris Phone #: ###-#### ok
ELE07-02495 Final9/7/20079/7/20079/7/2007 2:41:39 PMPPASS
chris Phone #: ###-#### ok
ELE07-02494 Final9/7/20079/7/20079/7/2007 2:41:25 PMPPASS
chris Phone #: ###-#### ok
ELE07-03122 Rough-In Permanent Service9/7/20079/7/20079/7/2007 1:45:15 PMPPASS
chris Phone #: ###-#### r/i p/s u/g new ok
ELE07-03121 Electrical Rough-In9/7/20079/7/20079/7/2007 1:19:14 PMPPASS
chris Phone #: ###-#### r/i ok
ELE07-02894 Rough-In Permanent Service9/7/20079/7/20079/7/2007 12:47:21 PMPPASS
dino Phone #: ###-#### ok corr made r/i p/s u/g new ok
ELE07-03094 Electrical Rough-In9/7/20079/7/20079/7/2007 12:19:32 PMPPASS
Jesse; Phone #: ###-#### Internet Inspection Request from: Hattie James ok
ELE06-02413 Final9/7/20079/7/20079/7/2007 12:19:12 PMPPASS
ok card signed
ELE07-02529 Electrical Rough-In9/6/20079/7/20079/7/2007 10:23:11 AMAPART
Cieling Inspection in Office/ Halllway for cover. Please call with any questions. Phone #: ###-#### Internet Inspection Request from: todd hall office and hall ceilings ok
ELE05-03536 Final9/6/20079/7/20079/7/2007 10:00:35 AMAFAIL
Please call Jim 30 min. prior@###-####. Phone #: ###-#### Internet Inspection Request from: Heather Packer corr fee due met contr. 210.52(C)(1)&(5) except shall install outlets for countertops and peninsular as codes noted states kit layout was changed after r/i inspection250.32 (B)(1) shall install phases,neut.,m and equip grd from service on fence to house, 250.52(A)(1) grd u/g water at house within 5ft, install 2 grd rods, 225.31,32,36 install service disconnect at either inside or outside upon entry , BCC&110.3(B) secure p/s at fence, and use only 2 pole breakers at milbank COW
ELE05-03536 Permanent Service9/7/20079/7/20079/7/2007 9:39:37 AMAFAIL
Please call Jim 30 min. prior@###-####. Phone #: ###-#### Internet Inspection Request from: Heather Packer see note for final inspection
ELE06-04230 Final9/6/20079/7/20079/7/2007 8:47:30 AMAPASS
Please call Michelle 30 min. prior@###-#### Phone #: ###-#### Internet Inspection Request from: Heather Packer ok
ELE07-02775 Permanent Service9/6/20079/7/20079/7/2007 8:36:39 AMAFAIL
jack Phone #: ###-#### Note: look at garaga also corr called left message needs GEC sized to T250.66 KCmil for 400 amps 250.52(A)(1) need covers for sub panels, need manufactures instruction , can they be use as subpanels or p/s only? neutral jumper removed