Inspections for the day of: Friday, September 7, 2007.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-03124 Temporary Service9/7/20079/7/20079/7/2007 3:56:41 PMPFAIL
###-#### Internet Inspection Request from: Todd Holbrook called, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 110.14(A) connection of conductors to a terminal shall ensure a thoroughly good connection (gec at transformer), fee due
ELE07-03085 Electrical Rough-In9/7/20079/7/20079/7/2007 3:20:07 PMPPASS
Scheduled by a contractor via Hello! on 9/7/2007 at 8:46:30 AM. Contact: ###-####. corrections made, ric ok, Note: no inspection made from house to garage for u/g
ELE07-03084 Electrical Rough-In9/7/20079/7/20079/7/2007 2:51:06 PMPPASS
Scheduled by a contractor via Hello! on 9/7/2007 at 8:45:33 AM. Contact: ###-####. corrections made, ric ok, Note: no inspection made from house to garage u/g
ELE07-03083 Electrical Rough-In9/7/20079/7/20079/7/2007 2:29:09 PMPPASS
Scheduled by a contractor via Hello! on 9/7/2007 at 8:44:38 AM. Contact: ###-####. corrections made, ric ok Note: no underground house to garage inspected
ELE07-03112 Final9/6/20079/7/20079/7/2007 1:54:25 PMPPASS
electrical service change with new grounding and verified range/dryer 4wire add a/c stub out back of house open Phone #: ###-#### Internet Inspection Request from: Brad Baker ok to final
ELE07-03112 Permanent Service9/7/20079/7/20079/7/2007 1:30:53 PMPPASS
electrical service change with new grounding and verified range/dryer 4wire add a/c stub out back of house open Phone #: ###-#### Internet Inspection Request from: Brad Baker p/s o/h rec ok
ELE07-03071 Rough-In Permanent Service9/7/20079/7/20079/7/2007 1:10:52 PMPCANC
Please call Todd (###-####) PRIOR to inspection to meet at site. Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson see conf
ELE07-03071 Conference9/7/20079/7/20079/7/2007 1:10:41 PMPDONE
Please call Todd (###-####) PRIOR to inspection to meet at site. Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson met contr, talked about grounding bushings at service, no ser in raceway, metal water pipe, 4-wire for range and dryer, clean area over top of panels, move or cap water pipe below panel
ELE07-02241 Final9/6/20079/7/20079/7/2007 12:39:07 PMPPASS
Dan; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to final, signed occ card
ELE07-02241 Electrical Rough-In9/7/20079/7/20079/7/2007 12:38:05 PMPPASS
Dan; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to cover ceiling
ELE07-03114 Electrical Rough-In9/6/20079/7/20079/7/2007 10:45:04 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton ric walls only ok
ELE07-02344 Final9/6/20079/7/20079/7/2007 10:13:58 AMAPASS
rick Phone #: ###-#### called contr to label disconnects, ok to final
ELE07-02766 Electrical Rough-In9/4/20079/7/20079/7/2007 9:27:08 AMAFAIL
Gene; Phone #: ###-#### Internet Inspection Request from: Hattie James met owner, left corr notice, nec 250.52(A)(3) shall provide concrete encased electrode encased by minimum 2" concrete, 312.5 all conductors entering enclosure shall have abrasion protection, 110.12(A) unused openings shall be closed, 408.4 circuit directory shall be clear, concise, and explanatory, 250.64(C) grounding electrode conductors shall be continuous without a splice, BCC shall provide electrical identification plate for voltage and amperage for building
ELE07-02547 Final9/7/20079/7/20079/7/2007 8:09:19 AMAPART
Contact is Cory. Final inspection for Tulley''s Coffee space only. Phone #: ###-#### Internet Inspection Request from: David Bonner ceiling area coffee only, no other work done in area, ok to cover ceiling, and part final this area only