ELE07-03124
| Temporary Service | 9/7/2007 | 9/7/2007 | 9/7/2007 3:56:41 PM | P | FAIL |
|
|
###-#### Internet Inspection Request from: Todd Holbrook called, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 110.14(A) connection of conductors to a terminal shall ensure a thoroughly good connection (gec at transformer), fee due
|
ELE07-03085
| Electrical Rough-In | 9/7/2007 | 9/7/2007 | 9/7/2007 3:20:07 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 9/7/2007 at 8:46:30 AM. Contact: ###-####. corrections made, ric ok, Note: no inspection made from house to garage for u/g
|
ELE07-03084
| Electrical Rough-In | 9/7/2007 | 9/7/2007 | 9/7/2007 2:51:06 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 9/7/2007 at 8:45:33 AM. Contact: ###-####. corrections made, ric ok, Note: no inspection made from house to garage u/g
|
ELE07-03083
| Electrical Rough-In | 9/7/2007 | 9/7/2007 | 9/7/2007 2:29:09 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 9/7/2007 at 8:44:38 AM. Contact: ###-####. corrections made, ric ok Note: no underground house to garage inspected
|
ELE07-03112
| Final | 9/6/2007 | 9/7/2007 | 9/7/2007 1:54:25 PM | P | PASS |
|
|
electrical service change with new grounding and verified range/dryer 4wire add a/c stub out back of house open Phone #: ###-#### Internet Inspection Request from: Brad Baker ok to final
|
ELE07-03112
| Permanent Service | 9/7/2007 | 9/7/2007 | 9/7/2007 1:30:53 PM | P | PASS |
|
|
electrical service change with new grounding and verified range/dryer 4wire add a/c stub out back of house open Phone #: ###-#### Internet Inspection Request from: Brad Baker p/s o/h rec ok
|
ELE07-03071
| Rough-In Permanent Service | 9/7/2007 | 9/7/2007 | 9/7/2007 1:10:52 PM | P | CANC |
|
|
Please call Todd (###-####) PRIOR to inspection to meet at site. Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson see conf
|
ELE07-03071
| Conference | 9/7/2007 | 9/7/2007 | 9/7/2007 1:10:41 PM | P | DONE |
|
|
Please call Todd (###-####) PRIOR to inspection to meet at site. Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson met contr, talked about grounding bushings at service, no ser in raceway, metal water pipe, 4-wire for range and dryer, clean area over top of panels, move or cap water pipe below panel
|
ELE07-02241
| Final | 9/6/2007 | 9/7/2007 | 9/7/2007 12:39:07 PM | P | PASS |
|
|
Dan; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to final, signed occ card
|
ELE07-02241
| Electrical Rough-In | 9/7/2007 | 9/7/2007 | 9/7/2007 12:38:05 PM | P | PASS |
|
|
Dan; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to cover ceiling
|
ELE07-03114
| Electrical Rough-In | 9/6/2007 | 9/7/2007 | 9/7/2007 10:45:04 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton ric walls only ok
|
ELE07-02344
| Final | 9/6/2007 | 9/7/2007 | 9/7/2007 10:13:58 AM | A | PASS |
|
|
rick Phone #: ###-#### called contr to label disconnects, ok to final
|
ELE07-02766
| Electrical Rough-In | 9/4/2007 | 9/7/2007 | 9/7/2007 9:27:08 AM | A | FAIL |
|
|
Gene; Phone #: ###-#### Internet Inspection Request from: Hattie James met owner, left corr notice, nec 250.52(A)(3) shall provide concrete encased electrode encased by minimum 2" concrete, 312.5 all conductors entering enclosure shall have abrasion protection, 110.12(A) unused openings shall be closed, 408.4 circuit directory shall be clear, concise, and explanatory, 250.64(C) grounding electrode conductors shall be continuous without a splice, BCC shall provide electrical identification plate for voltage and amperage for building
|
ELE07-02547
| Final | 9/7/2007 | 9/7/2007 | 9/7/2007 8:09:19 AM | A | PART |
|
|
Contact is Cory. Final inspection for Tulley''s Coffee space only. Phone #: ###-#### Internet Inspection Request from: David Bonner ceiling area coffee only, no other work done in area, ok to cover ceiling, and part final this area only
|