Inspections for the day of: Tuesday, September 7, 2010.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00225 INSP-Final Inspection9/7/20109/7/20109/7/2010 2:43:31 PMPFAIL
Rob and I went over the map requirements.
FIR10-00013 INSP-Final Inspection9/7/20109/7/20109/7/2010 2:43:08 PMPFAIL
Rob and I went over the map requirements.
BLD10-02029 FIRE-Final Inspection9/7/20109/7/20109/7/2010 2:38:51 PMPFAIL
Provide a sprinkler study of the existing fire sprinkler system to verify that it will adequate coverage for the intended storage arrangement and height as stated on the permit application.
MIS10-00226 FIR-Final9/7/20109/7/20109/7/2010 2:29:02 PMPFAIL
The partial height wall was rebuilt at 36" instead of the required 42"
BLD10-01385 FIRE-Final Inspection9/7/20109/7/20109/7/2010 12:50:57 PMPPASS
Life safety passed. Deficiencies such as incorrect door hardware and duct smoke detector testing will be addressed with the tenant improvement permit.
FIR10-00238 INSP-Final Inspection9/3/20109/7/20109/7/2010 10:13:46 AMAFAIL
The previous wall/draft stop/ needs to be removed out in the warehouse area and Storage Room 115 sprinkler pendants are too far down from the deck but still installed 8" above the t-bar/ceiling. Also in this room the flex ducting is creating alot of obstructions to the sprinkler coverage.