ELE09-01766
| ELE-Aging Inspection | 9/7/2011 | 9/7/2011 | 9/9/2011 6:22:34 AM | | DONE |
|
|
still under construction
|
ELE11-01080
| Final | 9/2/2011 | 9/7/2011 | 9/7/2011 2:56:41 PM | P | PASS |
|
|
Please Call Bryan at ###-#### when headed to site. Phone #: ###-#### >> Inspection requested via web by Bryan Atkins p/s o/h rec ok, ok final
|
ELE11-01651
| Final | 9/7/2011 | 9/7/2011 | 9/7/2011 2:55:39 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Tracy Robertson ok final
|
ELE11-02018
| Electrical Rough-In | 9/7/2011 | 9/7/2011 | 9/7/2011 2:43:27 PM | P | PASS |
|
|
Wayne Phone #: ###-#### ri ok
|
ELE11-01598
| Electrical Rough-In | 9/7/2011 | 9/7/2011 | 9/7/2011 2:43:25 PM | P | FAIL |
|
|
Warren / Luke ###-#### Please call before going out. Phone #: ###-#### met owner, showed 1 1/4", explained j-box shall be accessible, remove devices for free conductor inspection, add switch for entry light, strap flex by final
|
ELE11-02062
| Final | 9/7/2011 | 9/7/2011 | 9/7/2011 12:41:44 PM | P | CANC |
|
|
Inspect to have power turned back on. Call realitor to coordinate access at ###-####. Thanks Phone #: ###-#### >> Inspection requested via web by Eric Schroeder called contractor, told that he must see job before calling for inspection, he will recall
|
ELE11-01728
| Final | 9/6/2011 | 9/7/2011 | 9/7/2011 10:38:57 AM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Kathy Smith ok final
|
ELE11-02054
| Electrical Rough-In | 9/6/2011 | 9/7/2011 | 9/7/2011 10:27:32 AM | A | PASS |
|
|
rich Phone #: ###-#### ri ok
|
ELE11-01979
| Rough-In Permanent Service | 9/6/2011 | 9/7/2011 | 9/7/2011 9:18:39 AM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Todd Sellman see ri and final
|
ELE11-01979
| Final | 9/7/2011 | 9/7/2011 | 9/7/2011 9:18:26 AM | A | PASS |
|
|
ok to final
|
ELE11-01979
| Electrical Rough-In | 9/7/2011 | 9/7/2011 | 9/7/2011 9:17:54 AM | A | PASS |
|
|
ri ok
|
ELE11-02023
| Electrical Rough-In | 9/6/2011 | 9/7/2011 | 9/7/2011 8:52:38 AM | A | FAIL |
|
|
Partial rough-in, walls only. CJ is contact. Could you call contact in route and if we aren''t there, we will meet you. Thank you! Phone #: ###-#### >> Inspection requested via web by Chris Chesnut NEC 517, shall provide redundant grounding for exam rooms, close open ko, provide 1 1/4" for ent
|
ELE11-02061
| Electrical Rough-In | 9/6/2011 | 9/7/2011 | 9/7/2011 8:18:59 AM | A | PASS |
|
|
For access please call Ed 1/2 hr prior to inspection.###-#### >> Inspection requested via web by Terry Scott ri ok
|
ELE11-02033
| Permanent Service | 9/6/2011 | 9/7/2011 | 9/7/2011 7:42:56 AM | A | PASS |
|
|
Any questions, please call Clay. Thank You. Phone #: ###-#### >> Inspection requested via web by Clay Morgan p/s, exst meter pak, rec, ok
|