Inspections for the day of: Wednesday, September 7, 2011.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00422 INSP-Sprinkler Rough-in9/7/20119/7/20119/7/2011 3:35:05 PMPPASS
Rough-in spection passed. Piping can be covered
BLD11-00781 FIRE-Final Inspection9/6/20119/7/20119/7/2011 3:34:05 PMPFAIL
Project is not ready for a final inspection due to the project related fire alarm permit. Per Ron Amandus, it is ok for Winco to begin moving in the items that are to be stored in this warehouse. No finals will be given until the fire alarm and all related life safety items have passed inspection.
BLD11-01683 FIRE-Final Inspection9/2/20119/7/20119/7/2011 3:28:14 PMAFAIL
This project is not ready for a final inspection. Neither the project related fire alarm or fire sprinkler permits are ready for final.
FIR11-00430 INSP-Final Inspection9/7/20119/7/20119/7/2011 3:26:23 PMPFAIL
The gas to the hvac unit has not been turned on so the smoke detector could not be tested.
BLD11-01539 FIRE-Final Inspection9/6/20119/7/20119/7/2011 2:59:12 PMPPASS
Life safety passed.
FIR11-00386 INSP-Final Inspection9/7/20119/7/20119/7/2011 2:58:55 PMPPASS
Permit finaled
FIR11-00370 INSP-Final Inspection9/6/20119/7/20119/7/2011 2:58:36 PMPPASS
Permit finaled. The previous corrections listed have been completed.
FIR11-00419 INSP-Alarm Testing9/6/20119/7/20119/7/2011 10:12:37 AMAFAIL
No testing was performed. The duct smoke detector is mounted incorrectly and will need to be relocated to the narrow side of the duct prior to testing. The hood suppression system was not tested due to the hood suppression contractor not being on site.
FIR11-00386 INSP-Final Inspection9/6/20119/7/20119/7/2011 9:13:46 AMAFAIL
No access to the fire alarm panel. No inspection was performed.