Inspections for the day of: Wednesday, September 7, 2016.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00502 INSP-Sprinkler Rough-in/Hydro9/7/20169/7/20169/7/2016 1:43:18 PMPFAIL
The installation does not match plans. Resubmittals are required per the review notes due to the safety factor of the hydraulic calculations. I noted numerous pipe routing changes, added fittings and pendant heads spaced at 16' apart. Riser has not been built yet and the underground supply piping has not been installed yet. Rough-in inspection and hydro test stopped due to the issues.
BLD15-04264 FIRE-Final Inspection9/7/20169/7/20169/7/2016 1:40:33 PMPPASS
life safety passed
FIR16-00474 INSP-Final Inspection9/1/20169/7/20169/7/2016 11:15:50 AMAPASS
Permit finaled
FIR16-00476 INSP-Final Inspection9/1/20169/7/20169/7/2016 11:15:36 AMAPASS
Permit finaled
FIR16-00475 INSP-Final Inspection9/1/20169/7/20169/7/2016 11:15:24 AMAPASS
Permit finaled
FIR16-00364 INSP-Sprinkler Rough-in/Hydro9/6/20169/7/20169/7/2016 10:14:10 AMAPASS
Overhead hydro of all three floors passed.
BLD16-03002 FIRE-Final Inspection9/6/20169/7/20169/7/2016 10:05:49 AMAPASS
Life safety passed