| ELE-Conference | 9/7/2017 | 9/7/2017 | 9/7/2017 2:59:15 PM | P | FAIL |
|
|
Kristi Phone #: ###-#### 200.4- Grounded conductor of a multiwire branch circuit shall carry only the unbalanced load. Both ungrounded conductors on same phase. Possible overload of grounded conductor. 210.23- Appliances or electrical equipment fastened in place shall not exceed 50% of the rating of branch circuit. Window mounted AC units and bath fan/light/heater combo all require dedicated circuits. Circuit overload causing sparks and smell of smoke. 400.8- Flexible cords shall not run through walls or doorways. 16-3 runs from living room to bedroom for window mounted AC unit which is burned up. BCC 04-05-15- Licensed contractor required for repairs. Homeowners exemption does not apply to rental units.
|
ELE17-02813
| Rough-In Permanent Service | 9/6/2017 | 9/7/2017 | 9/7/2017 1:46:19 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Rough in ok cover p/s u/g n ok
|
ELE17-02814
| Rough-In Permanent Service | 9/6/2017 | 9/7/2017 | 9/7/2017 1:44:24 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Rough in ok cover p/s u/g n ok
|
ELE17-02909
| Rough-In Permanent Service | 9/6/2017 | 9/7/2017 | 9/7/2017 1:43:47 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Rough in ok cover p/s u/g n ok
|
ELE17-02168
| Electrical Rough-In | 9/7/2017 | 9/7/2017 | 9/7/2017 1:02:53 PM | P | PASS |
|
|
Floor heat master bedroom Phone #: ###-#### Inspection requested via web by Zane Robertson Rough in ok cover
|
ELE17-02926
| Final | 9/6/2017 | 9/7/2017 | 9/7/2017 11:55:25 AM | A | FAIL |
|
|
Water only - Randy Phone #: ###-#### 352.30(B)- PVC conduit shall be securely fastened in place at intervals not to exceed 3' for 3/4" PVC. In crawl space.
|
ELE17-02954
| Conference | 9/6/2017 | 9/7/2017 | 9/7/2017 11:14:37 AM | A | DONE |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Discussed the protection of electrical equipment where water and sprinkler piping previously installed above, The reusing of TC cable system from 1992 installation, and meeting room requirements. Drip pans shall be installed to protect electrical equipment. #10 TC cable shall be reused if compliant with articles 336 and 392.80. Collabrative rooms over 215 sq. ft. shall comply with 210.71 for floor receptacles and wall space requirements.
|
ELE17-02168
| Electrical Rough-In | 9/6/2017 | 9/7/2017 | 9/7/2017 9:51:46 AM | A | FAIL |
|
|
Floor heat in master bedroom Phone #: ###-#### Inspection requested via web by Zane Robertson 110.3- Cold lead splice shall be located in floor system and be recessed in floor to avoid damage as per manufacturers instructions. 424.38(B)(4)- Heating cable shall not be installed in a wall.
|
ELE17-02210
| Electrical Rough-In | 9/7/2017 | 9/7/2017 | 9/7/2017 9:21:04 AM | A | PASS |
|
|
Is it possable to do this 8:30 - 9:30 am ish? Phone #: ###-#### Inspection requested via web by Mark M Grid rough in ok cover
|
ELE17-01549
| Electrical Rough-In | 9/6/2017 | 9/7/2017 | 9/7/2017 8:51:51 AM | A | PASS |
|
|
Linear lights. 9am pour. Shane is the contact his cell no. is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates Additional 2 on edge of band south 1/2 rough in ok cover
|
ELE17-02950
| Final | 9/6/2017 | 9/7/2017 | 9/6/2017 2:48:47 PM | A | CANC |
|
|
Final inspection for temp. power pole Phone #: ###-#### Inspection requested via web by Clint Tate needed temp service
|