Inspections for the day of: Thursday, September 8, 2005.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-01777 Final9/8/20059/8/20059/8/2005 4:18:14 PMPPASS
Bob, this is another one that the house is finaled and the temp pole failed. Let me know if you have questions. Thanks Rita ###-#### corrections not made, pole not connected, they used another source for power. ok to final
ELE05-01572 Final9/8/20059/8/20059/8/2005 4:12:13 PMPPASS
Bob, this is for a temp pole, the house has a final done on it can you final this temp pole permit? ok to final
ELE05-02915 Final9/8/20059/8/20059/8/2005 4:00:25 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Clyde Logan ok to final
ELE05-03014 Electrical Rough-In9/8/20059/8/20059/8/2005 2:34:32 PMPPASS
loren; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr to strap 1 mc cable in nw wall, ric walls only ok
ELE05-03272 Temporary Service9/7/20059/8/20059/8/2005 1:41:49 PMPNR
###-#### - nicole called contr, no address, no yellow signs, truck just pulled up to set pole, told to recall, fee due
ELE05-03274 Electrical Rough-In9/8/20059/8/20059/8/2005 1:19:14 PMPPASS
Scheduled by a contractor via Hello! on 9/8/2005 at 10:45:28 AM. Contact: ###-####. ric walls ok
ELE05-03032 Final9/8/20059/8/20059/8/2005 12:47:11 PMPPASS
allen; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ok to final
ELE05-03006 Final9/8/20059/8/20059/8/2005 12:38:31 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Clyde Logan ok to final
ELE05-03263 Final9/7/20059/8/20059/8/2005 10:51:43 AMAPASS
ok to final
ELE05-03263 Electrical Rough-In9/7/20059/8/20059/8/2005 10:51:17 AMAPASS
###-#### ric ok
ELE05-03268 Permanent Service9/7/20059/8/20059/8/2005 10:26:45 AMANR
###-#### - chuck called contr to have pedestal rotated for clearance
ELE05-03270 Rough-In Permanent Service9/7/20059/8/20059/8/2005 10:02:11 AMACANC
###-#### - rocky see note for r/i
ELE05-03270 Electrical Rough-In9/7/20059/8/20059/8/2005 10:01:27 AMAFAIL
###-#### - rocky called contr, left corr notice, 330.30(B) mc cable shall be strapped within 12" of box. BCC address shall be provided,meter socket shall be identified. will fix and recall.
ELE05-00975 Final9/7/20059/8/20059/8/2005 9:16:26 AMAPASS
allen; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr to fix 2 rcpts with open gnds. ok to final
ELE05-02915 Final9/8/20059/8/20059/8/2005 8:57:12 AMAPART
Phone #: ###-#### Internet Inspection Request from: Clyde Logan need to check gfci in bathrooms only. rest ok.
ELE05-03006 Final9/8/20059/8/20059/8/2005 8:55:52 AMANR
Phone #: ###-#### Internet Inspection Request from: Clyde Logan called contr, needs disposal wired, a/c wired, panel schedule, and add recpt in mbr. will call back in. sticker is on panel.
ELE05-02301 Final9/7/20059/8/20059/8/2005 8:14:38 AMAPASS
###-#### - allen Note: please call 1/2 hr prior to inspection called contr to use gfci by utility sink. ok to final
ELE05-03266 Permanent Service9/7/20059/8/20059/8/2005 8:08:46 AMAPASS
###-#### - chuck p/s u/g exst ok