Inspections for the day of: Thursday, September 8, 2005.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00080 INSP-Alarm Testing9/7/20059/8/20059/12/2005 2:59:19 PMACANC
Phone #: ###-#### Internet Inspection Request from: Wayne Berry Cancel inspection per conversation with Wayne.
FIR05-00080 INSP-Sprinkler Rough-in/Hydro9/7/20059/8/20059/12/2005 2:57:59 PMACANC
Phone #: ###-#### Internet Inspection Request from: Wayne Berry Cancel inspection per conversation with Wayne.
FIR05-00527 INSP-Final Inspection9/8/20059/8/20059/9/2005 4:57:15 PMPFAIL
One head as shown on approved plans is not installed in the reception area, review notes and submitted plans do not include the flex heads as used throughout the space.
BLD05-01316 FIRE-Final Inspection9/8/20059/8/20059/8/2005 3:43:55 PMPFAIL
Install fire extinguisher with current tag as discussed, need to test HVAC duct smoke detectors, fire alarm must be finaled prior to life safety sign off.
FIR05-00315 INSP-Supply line flush9/8/20059/8/20059/8/2005 3:35:57 PMPPART
Underground fire supply line flush is satisfactory.
BLD05-00223 FIRE-Final Inspection9/8/20059/8/20059/8/2005 3:34:22 PMPPASS
Life safety is satisfactory.
MIS05-00125 FIR-Final9/8/20059/8/20059/8/2005 2:42:03 PMPPASS
Life safety is acceptable.
FIR05-00326 INSP-Sprinkler Rough-in9/8/20059/8/20059/8/2005 1:53:51 PMPPART
The upright heads above hard lid areas on 2nd floor hall in front of the restrooms are okay to cover.
BLD04-01909 FIRE-Final Inspection9/7/20059/8/20059/8/2005 1:51:28 PMAPART
All fire life safety issues are satisfactory except for two doors, one at the mechanical room and one at an exterior storage room, which have non ADA approved hardware. Per Ken the GC the parts are on order and an inspection will be called in when installed, a temporary occupancy has been approved.
FIR05-00044 INSP-Final Inspection9/7/20059/8/20059/8/2005 1:39:17 PMPPASS
Fire alarm permit finaled.
FIR05-00549 INSP-Sprinkler Rough-in/Hydro9/8/20059/8/20059/8/2005 11:33:12 AMAPART
Overhead fire sprinkler rough-in is good for cover, will final when ceiling tile has been installed.
FIR03-00742 INSP-Final Inspection9/7/20059/8/20059/8/2005 11:06:03 AMAFAIL
The sample tube on HVAC duct smoke detector #7 is too short, smoke detector at the FACP is not correctly spaced above the panel for its intended function.
BLD05-01347 FIRE-Final Inspection9/7/20059/8/20059/8/2005 9:36:08 AMAFAIL
###-#### - terry Need to provide signage above both main entry/exit doors, provide visual indicators of the lock condition at both main entry/exit doors, provide and install fire extinguisher with current tag as discussed.
MIS05-00115 FIR-Final9/8/20059/8/20059/8/2005 12:00:00 AMPPASS
Fire life safety is satisfactory.
BLD05-01347 FIRE-Final Inspection9/8/20059/8/20059/8/2005 12:00:00 AMPPASS
Life safety passed inspection.
BLD05-01768 FIRE-Final Inspection9/7/20059/8/20059/7/2005 3:26:57 PMACANC
Phone #: ###-#### Internet Inspection Request from: Wayne Berry Inspection cancelled from web by: Wayne Berry
BLD05-00225 FIRE-Final Inspection9/7/20059/8/20059/7/2005 3:26:19 PMACANC
Phone #: ###-#### Internet Inspection Request from: Wayne Berry Inspection cancelled from web by: Wayne Berry
FIR05-00379 INSP-Alarm Testing9/7/20059/8/20059/7/2005 3:24:21 PMACANC
Phone #: ###-#### Internet Inspection Request from: Wayne Berry Inspection cancelled from web by: Wayne Berry
FIR05-00066 INSP-Final Inspection9/7/20059/8/20059/7/2005 3:23:40 PMACANC
Phone #: ###-#### Internet Inspection Request from: Wayne Berry Inspection cancelled from web by: Wayne Berry