Inspections for the day of: Friday, September 8, 2006.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00367 FIR-Aging Inspection9/8/20069/8/20069/15/2006 9:37:44 AM NR
Per Charlie the work is complete, they are just waiting to get the st. als project completed first
FIR06-00641 INSP-Sprinkler Rough-in/Hydro9/7/20069/8/20069/8/2006 4:53:29 PMPPASS
Underground supply is ok to bury.
FIR06-00544 INSP-Final Inspection9/7/20069/8/20069/8/2006 4:52:55 PMPPASS
Sprinkler piping in hard lid areas in main lobby and the closets is ok to cover. A sign will be needed on ceiling tiles for elevator pit control valve location.
FIR06-00457 INSP-Final Inspection9/7/20069/8/20069/8/2006 2:55:45 PMPPASS
Permit finaled
FIR05-00272 INSP-Sprinkler Rough-in/Hydro9/7/20069/8/20069/8/2006 2:36:36 PMPCANC
No time for the hydro test today
FIR05-00403 INSP-Sprinkler Rough-in9/7/20069/8/20069/8/2006 2:09:42 PMPFAIL
The piping sizing in the end garage where the remote area is does not match plan. Plan shows 1" piping but 2" is installed. Also the 3rd floor remote area has a piping size problem as well and has been marked on the plans. No tenting has been done yet either. I gave Kennie permision to cover everything but the end garage and entire third floor until revised hydraulic calculations are provided and a tenting inspection is done.
FIR06-00616 INSP-Sprinkler Rough-in9/7/20069/8/20069/8/2006 1:45:43 PMAPASS
The remaining underground supply piping is ok to cover.
FIR06-00346 INSP-Sprinkler Rough-in/Hydro9/5/20069/8/20069/8/2006 12:29:54 PMAFAIL
Hydro test failed. Guage appeared to have lost 2-3 psi from 10:15am to 12:15pm.
BLD06-01488 FIRE-Final Inspection9/7/20069/8/20069/8/2006 11:52:44 AMAFAIL
See the original correction notice for remaining items that did not get corrected which include the repair of the exit sign at the north east exit door, mounting of the fire extinguishers and the correct sticker at the south main exit door.
FIR06-00617 INSP-Sprinkler Rough-in9/7/20069/8/20069/8/2006 11:08:14 AMAPASS
The remaining underground is ok for cover
FIR06-00361 INSP-Final Inspection9/6/20069/8/20069/8/2006 9:26:43 AMAPASS
Permit finaled
FIR06-00656 INSP-Final Inspection9/7/20069/8/20069/8/2006 8:56:26 AMAPASS
Permit finaled
FIR05-00724 INSP-Final Inspection9/7/20069/8/20069/8/2006 8:55:05 AMAPASS
Permit finaled. Contractor needs to install head guards on the sidewall heads
FIR06-00641 INSP-Sprinkler Rough-in/Hydro9/7/20069/8/20069/7/2006 3:57:02 PMACANC
Contact: Todd - Cover Inspection; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley