Inspections for the day of: Friday, September 8, 2006.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorWilliam E Thomas
TitleELE-INSPECTOR
Phone #794-9492
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-02878 Final9/8/20069/8/20069/8/2006 4:09:50 PMPPASS
steve; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to final
ELE06-02946 Electrical Rough-In9/8/20069/8/20069/8/2006 2:27:39 PMAPART
upstairs addition ready for RI and underground to garage thanks; Phone #: ###-#### Internet Inspection Request from: Don Lustig
1. upstairs and underground for new electrical work ok
2. conduit depth for existing spa conduit at 6", needs to be at 18".
ELE06-03348 Rough-In Permanent Service9/8/20069/8/20069/8/2006 2:25:46 PMPPASS
Internet Inspection Request from: Latisha Peltier
1. ri ok
2. p/s u/g n ok
ELE06-03303 Rough-In Permanent Service9/8/20069/8/20069/8/2006 2:24:55 PMPPASS
This is for a ufer inspection.; Phone #: ###-#### Internet Inspection Request from: Tracy Robertson
1. ufer ok
2. p/s u/g n ok 2meters required
ELE06-01995 Electrical Rough-In9/8/20069/8/20069/8/2006 11:53:46 AMPPASS
wes Note: underground; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
1. underground ok into the building
ELE06-03318 Electrical Rough-In9/7/20069/8/20069/8/2006 11:52:27 AMAPASS
Paul Klindt; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy
ri ok
ELE06-02971 Final9/7/20069/8/20069/8/2006 11:51:59 AMAPASS
Store does not open until 9:30. Contact Matt White if there are any questions.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz
ELE06-03341 Electrical Rough-In9/7/20069/8/20069/8/2006 11:51:46 AMAFAIL
shawn NOTE: he will be there by 9:00 am to walk with you; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
1. no prints on job
2. 210.52- recep spacing throughout the house.
3. shall have another roughin with the prints on reinspection