Inspections for the day of: Monday, September 8, 2008.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-01901 Rough-In Permanent Service9/8/20089/8/20089/8/2008 4:08:42 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS called, left correction notice, NEC 250.94 shall provide intersystem bonding termination, 110.12(A) unused openings shall be closed in panel, 348.26 there shall not be over 360 degree bends in fmc, 330.30(B) mc shall be secured within 12" of termination, 300.14 there shall be at least 6" free conductor left in each box (mezzanine), 300.4(D) shall provide 1 1/4" to raceway from edge of framing member, 110.26(F)(1) ducts shall not be in dedicated space above panel, BCC shall have approved set of plans on job, separate permit shall be provided for each meter location, shall post job id sticker, shall post job address
ESC08-00238 General Inspection9/8/20089/8/20089/8/2008 3:26:58 PMPPART
looked ok
ESC08-00155 General Inspection9/8/20089/8/20089/8/2008 3:25:52 PMPPART
looked ok
ESC08-00282 General Inspection9/8/20089/8/20089/8/2008 3:24:54 PMAPART
looked ok
ESC08-00175 General Inspection9/8/20089/8/20089/8/2008 3:21:21 PMAPART
looked ok
ESC08-00490 General Inspection9/8/20089/8/20089/8/2008 3:19:51 PMAPART
looked ok
ELE08-01773 Rough-In Permanent Service9/8/20089/8/20089/8/2008 2:27:20 PMPPASS
justin - please call 1/2 hr prior Phone #: ###-#### ric ok/ p/s o/h n ok
ELE08-02104 Permanent Service9/8/20089/8/20089/8/2008 1:37:31 PMPPASS
ROBERT Phone #: ###-#### p/s o/h rec ok, no esc this project
ELE08-02428 Conference9/2/20089/8/20089/8/2008 12:40:17 PMPDONE
Internet Inspection Request from: Adam Staigle talked about service for tenant spaces and sub-panels, permits for separate spaces, probably won't need any service work at this time, but will later, 1 subpanel will work for remodel at this time, no esc this project
ELE08-01696 Final9/5/20089/8/20089/8/2008 10:32:09 AMAPART
Final inspection. Please call Bob Johnston. Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson looked at installation, called contractor, need to have 315 or 324 look at pre-fab structure
ELE08-02468 Electrical Rough-In9/7/20089/8/20089/8/2008 9:21:26 AMAPASS
inspect undergroung conduit for cover Phone #: ###-#### Internet Inspection Request from: Andy Derrick u/g house to garage ok to cover
ELE08-01312 Final9/5/20089/8/20089/8/2008 8:37:47 AMAPASS
Homeowner will be home untill at least 10 am monday for inspection. Phone #: ###-#### Internet Inspection Request from: Cevyn Recla called contractor about polarity for bath gfci, rest ok, ok to final, no esc this project
ELE08-02208 Electrical Rough-In9/5/20089/8/20089/8/2008 8:06:47 AMAPART
dale- underground Phone #: ###-#### ok to cover u/g from temp pole south toward street- will put splice box in planter, will cut street later for generator feeders