FIR09-00354
| FIR-Aging Inspection | 9/8/2009 | 9/8/2009 | 9/9/2009 2:46:22 PM | | DONE |
|
|
Pending site inspection request for permit final.
|
FIR09-00386
| INSP-Final Inspection | 9/8/2009 | 9/8/2009 | 9/8/2009 3:34:32 PM | P | FAIL |
|
|
Seven manual pull stations are mounted too high-see fire code review note #9, two 75cd notification appliances are overspaced at the return bay, one 110cd appliance is overspaced per install and red lined note on stamped plan set- see note #1, main drain vavle at the sprinkler riser need not be supervised, explosion proof strobes at the fuel bay are missing, overspaced notification per plan review annotations at the return bay, provide "NFPA 72 Record of Inspection and Testing" per note #3, provide a lock and label at the panel circut breaker-note #8. No further testing completed at this time until repairs are finished.
|
FIR09-00260
| INSP-Sprinkler Rough-in/Hydro | 9/8/2009 | 9/8/2009 | 9/8/2009 3:24:23 PM | P | PART |
|
|
Overhead hydrostatic testing passed, final pending project related fire alarm permit work, main drain valve does not need to be electricaly supervised, need "911" sign at the outside bell.
|
BLD09-01365
| FIRE-Final Inspection | 9/4/2009 | 9/8/2009 | 9/8/2009 11:45:08 AM | A | PASS |
|
|
Correction notice items field verified for completion, fire life safety finaled.
|
BLD09-01244
| FIRE-Final Inspection | 9/4/2009 | 9/8/2009 | 9/8/2009 11:44:04 AM | A | PASS |
|
|
Fire life safety inspection passed. Note: manual thumbturn at the exit door from the S1 side of the tenant space to be removed in order to comply with IFC 2006 1008.1.8.5 proir to structural final as discussed.
|
BLD09-01476
| FIRE-Final Inspection | 9/8/2009 | 9/8/2009 | 9/8/2009 11:04:23 AM | A | FAIL |
|
|
The hood suppression system, K class extinguisher and 2A 10BC fire extinguishers are due certification/annual inspection.
|
BLD08-02249
| FIRE-Final Inspection | 9/8/2009 | 9/8/2009 | 9/8/2009 11:02:25 AM | A | PART |
|
|
Life safety inspection for unit 556 passed, missing door hardware to be installed prior to final.
|