Inspections for the day of: Tuesday, September 8, 2009.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00365 FIR-Aging Inspection9/8/20099/8/20099/10/2009 9:00:04 AM NR
work is in progress per jeff
BLD09-01292 FIRE-Final Inspection9/8/20099/8/20099/8/2009 4:01:37 PMPPASS
Life safety passed.
BLD09-01508 FIRE-Final Inspection9/8/20099/8/20099/8/2009 2:52:10 PMPPASS
Life safety passed.
BLD09-01130 FIRE-Final Inspection9/8/20099/8/20099/8/2009 2:51:37 PMPPASS
Life safety passed.
FIR07-01032 INSP-Sprinkler Rough-in9/4/20099/8/20099/8/2009 2:51:01 PMAPASS
See the city approved plans for the piping that is ok for cover.
BLD09-00835 FIRE-Final Inspection9/4/20099/8/20099/8/2009 11:40:23 AMAFAIL
The hvac unit in the back of the store burnt a component while testing and would not start. The duct detector at the front of the store tested ok.
FIR09-00511 INSP-Final Inspection9/4/20099/8/20099/8/2009 11:39:25 AMAFAIL
The hvac unit in the northeast corner of the building has two duct smoke detectors that are not connected to the existing fire alarm system as required per IFC 907.12. There is also a hvac unit located in the center of the building that has a duct smoke detector located on the supply side that is not connected to the existing fire alarm system as per IFC 907.12. The remaining units tested ok for shutdown and reported to the central station. A re-inspection fee is being added for the upcoming fourth inspection.
BLD09-00057 FIRE-Final Inspection9/4/20099/8/20099/8/2009 11:21:15 AMAPASS
Life safety passed.