Inspections for the day of: Thursday, September 8, 2016.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-00255 ELE-Aging Inspection9/8/20169/8/20169/9/2016 4:38:07 PM PASS
Waiting on contractor
ELE09-01607 ELE-Aging Inspection9/8/20169/8/20169/9/2016 4:26:19 PM PASS
Unable to locate phone number
ELE16-02886 Rough-In Permanent Service9/7/20169/8/20169/8/2016 4:06:16 PMANR
Dual 200 meter base ; grounding. Phone #: ###-#### Inspection requested via web by David McClellan
Will reschedule for 9-9-16. Location of service will be in conflict if rezoned for town houses it is located on what would be property line and dividing wall. No penetrations in 2 hour firewall.
ELE15-01348 Electrical Rough-In9/6/20169/8/20169/8/2016 3:48:16 PMPPASS
elevator lobby ceilings, levels 6-9. call Frank Phone #: ###-#### Inspection requested via web by Brandon Robinson
9th floor elevator lobby not ready. 6, 7, 8th floor elevator lobby ceilings rough in ok cover.
ELE16-02600 Electrical Rough-In9/8/20169/8/20169/8/2016 2:47:42 PMPCANC
Dave. 1st floor lobby bathrooms ; 2nd floor common area wall cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy Duplicate request.
ELE16-02600 Electrical Rough-In9/8/20169/8/20169/8/2016 2:47:08 PMPPASS
Dave. 1st floor lobby bathrooms ; 2nd floor common area wall cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy
1st floor conference rm, west elevator lobby walls and hardlids, bathroom walls and hardlids, valet walls.
2nd floor offices, gym, bath walls and hardlids, hospitality rm wall and hardlid, hold on hospitality bath ceiling accesses not framed yet. areas noted rough in ok cover
ELE16-02600 Conference9/7/20169/8/20169/8/2016 2:39:42 PMPDONE
Sean. Design team wanted to conference on additional outlets requested under 210.60. Can you call 1/2 hour prior to heading to the site. Phone #: ###-#### Inspection requested via web by Sean DeLacy
Will meet 9-10-16 9 am to sign off on room layouts when furniture is visible on drawings.
ELE16-00089 Electrical Rough-In9/8/20169/8/20169/8/2016 11:50:33 AMAPASS
Call Bob for inspection of 2nd floor soffits. Phone #: ###-#### Inspection requested via web by Rafael Castillo
District kitchen transformer, Generator on floor 3 parking garage grounding corrected, and level 2 stair 5 lobby soffit cans rough in ok cover
ELE14-01611 Final9/7/20169/8/20169/8/2016 11:16:51 AMAFAIL
call dave for access ###-#### Phone #: ###-#### Inspection requested via web by danny perrine
210.52- A receptacle outlet shall be located at end of peninsula in kitchen.
300.15- Washer wire hanging in basement shall be secured and installed in a box and trimmed.
334.30- 10-3 for dryer shall be secured and box mounted.
400.8- Extension cord feeding washer shall be removed.
408.4- Panel covers shall be installed and labelled.
ELE16-02855 Electrical Rough-In9/7/20169/8/20169/8/2016 10:39:46 AMAPASS
We will be onsite and will meet you there. Phone #: ###-#### Inspection requested via web by Matthew Dunay
Listing confirmed rough in ok
ELE16-02859 Permanent Service9/7/20169/8/20169/8/2016 8:26:55 AMAPASS
Phone #: ###-#### Inspection requested via web by Tracy Robertson
p/s u/g n ok