Inspections for the day of: Friday, September 8, 2017.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-02810 Final9/8/20179/8/20179/8/2017 3:21:02 PMPPASS
Call Gary when in route if possible. Obtain visitors badge at front desk. Phone #: ###-#### Inspection requested via web by Steve McCloy
No card posted. Final ok
ELE17-02810 Electrical Rough-In9/8/20179/8/20179/8/2017 3:09:40 PMPPASS
Call Gary when in route if possible. Obtain visitors badge at front desk. Phone #: ###-#### Inspection requested via web by Steve McCloy
All wiring fished in. rough in ok.
ELE17-02965 Rough-In Permanent Service9/8/20179/8/20179/8/2017 3:09:02 PMPPASS
###-####
Rough in ok cover p/s u/g n ok
ELE17-02970 Electrical Rough-In9/7/20179/8/20179/8/2017 2:20:00 PMPPASS
Phone #: ###-#### Inspection requested via web by Cindie Swaim
At time of inspection rack system and array panels being installed. No raceways or wiring to service installed yet.
Listing confirmed on enphase micro inverters and panels. rough in ok
ELE17-02569 Electrical Rough-In9/7/20179/8/20179/8/2017 1:41:32 PMPPASS
Requesting a Ceiling Grid inspection for PM tomorrow. Please call Lynn prior to inspection. Phone #: ###-#### Inspection requested via web by Lynn Proctor
South fitness area grid only rough in ok cover
ELE16-03932 Electrical Rough-In9/8/20179/8/20179/8/2017 12:20:21 PMAPASS
dropped lids units 723-725, units 728-732 Phone #: ###-#### Inspection requested via web by Cathy Duchek
Rooms noted signed off in office. Rough in ok cover
ELE17-02791 Electrical Rough-In9/8/20179/8/20179/8/2017 11:56:32 AMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
11th floor wall rough in ok cover
ELE17-02862 Electrical Rough-In9/7/20179/8/20179/8/2017 11:40:31 AMAPASS
UFER grounding Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Concrete encased electrode and N.W. basement wall pour rough in ok cover.
ELE17-02724 Electrical Rough-In9/7/20179/8/20179/8/2017 11:30:42 AMACANC
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Wrong permit requested needed 11th floor on different permit.
ELE17-02926 Final9/7/20179/8/20179/8/2017 10:05:45 AMAPASS
Randy Phone #: ###-####
Final ok
ELE17-02926 Electrical Rough-In9/8/20179/8/20179/8/2017 10:05:32 AMPPASS
Randy Phone #: ###-####
Underground to well rough in ok cover
ELE17-02939 Temporary Service9/7/20179/8/20179/8/2017 9:46:16 AMAPASS
Phone #: ###-#### Inspection requested via web by Ben Grundhauser
t/s u/g n ok
ELE17-02965 Rough-In Permanent Service9/7/20179/8/20179/8/2017 9:28:20 AMAPART
Phone #: ###-#### Inspection requested via web by Alan Lusk
110.3- Branch circuit for furnace shall be sized as per manufacturers instructions.
15 amp installed 20 amp and 12 ga. required. Contactor to check with manufacturer for correct circuit.
408.3(B)(2)- Barriers shall be in place at line side termination of panel board.
OK insulate only