Inspections for the day of: Thursday, September 9, 2004.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00314 FIR-Aging Inspection9/9/20049/9/20049/9/2004 12:00:00 AM PASS
Will schedule for next week 9/10/2004 9:25:14 AM
FIR02-00411 INSP-Final Inspection9/7/20049/9/20049/9/2004 12:00:00 AMAFAIL
robert; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie Need additional pull at exit door to stair C in area E; need speaker/strobe in Horizon Ops and mechanical for AHU 5; as-builts needed at final to plan review; record of completion needed at final 9/9/2004 11:52:06 AM
BLD04-00572 FIRE-Final Inspection9/8/20049/9/20049/9/2004 12:00:00 AMAFAIL
jack; Phone #: ###-#### Internet Inspection Request from: Annette Moore Add exit sign as shown on plans; complete door hardware and rated doors need closures and latch; need to test duct detectors for AHU shutdown; emergency/exit lights okay 9/9/2004 8:28:23 AM
FIR04-00392 INSP-Alarm Testing9/8/20049/9/20049/9/2004 12:00:00 AMPPASS
Cell phone ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino
FIR04-00440 INSP-Final Inspection9/8/20049/9/20049/9/2004 12:00:00 AMPPASS
Cell PH. ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino
FIR04-00055 INSP-Final Inspection9/8/20049/9/20049/9/2004 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 9/8/2004 at 11:06:06 AM. Contact: ###-####. Wrong strobes installed in elevator lobbies 9/10/2004 9:25:53 AM
FIR04-00419 INSP-Final Inspection9/8/20049/9/20049/9/2004 12:00:00 AMPPASS
###-####-- mark Second and third floors okay - per plans; need to complete FIR04-00055 per agreement 9/10/2004 9:27:15 AM
BLD04-00553 FIRE-Final Inspection9/9/20049/9/20049/9/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 9/9/2004 at 7:50:45 AM. Contact: ###-####. Card/plans are in new office; sprinklers/alarms were okay without modifications 9/9/2004 2:52:06 PM
BLD04-00572 FIRE-Final Inspection9/9/20049/9/20049/9/2004 12:00:00 AMPPASS
jack; Phone #: ###-#### Internet Inspection Request from: Annette Moore GC will have door hardware/closures for structural inspector as they weren't completed 9/9/2004 2:36:36 PM
BLD03-02673 FIRE-Final Inspection9/9/20049/9/20049/9/2004 12:00:00 AMPFAIL
john; Phone #: ###-#### Internet Inspection Request from: Annette Moore Front door to be keyed both sides; basement doors need hardware per plans 9/9/2004 3:09:20 PM
FIR04-00461 INSP-Final Inspection9/9/20049/9/20049/9/2004 12:00:00 AMPPASS
Installed per plans; the system lacks a smoke detector above the panel; strobes not sync'd and not temporal but are outside the TI area 9/9/2004 12:08:52 PM
FIR04-00461 INSP-Final Inspection9/9/20049/9/20049/9/2004 12:00:00 AMPPASS
Installed per plans; the system lacks a smoke detector above the panel; strobes not sync'd and not temporal but are outside the TI area 9/9/2004 12:08:59 PM
BLD04-01244 FIRE-Final Inspection9/9/20049/9/20049/9/2004 12:00:00 AMPPASS