FIR04-00314
| FIR-Aging Inspection | 9/9/2004 | 9/9/2004 | 9/9/2004 12:00:00 AM | | PASS |
|
|
Will schedule for next week 9/10/2004 9:25:14 AM
|
FIR02-00411
| INSP-Final Inspection | 9/7/2004 | 9/9/2004 | 9/9/2004 12:00:00 AM | A | FAIL |
|
|
robert; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie Need additional pull at exit door to stair C in area E; need speaker/strobe in Horizon Ops and mechanical for AHU 5; as-builts needed at final to plan review; record of completion needed at final 9/9/2004 11:52:06 AM
|
BLD04-00572
| FIRE-Final Inspection | 9/8/2004 | 9/9/2004 | 9/9/2004 12:00:00 AM | A | FAIL |
|
|
jack; Phone #: ###-#### Internet Inspection Request from: Annette Moore Add exit sign as shown on plans; complete door hardware and rated doors need closures and latch; need to test duct detectors for AHU shutdown; emergency/exit lights okay 9/9/2004 8:28:23 AM
|
FIR04-00392
| INSP-Alarm Testing | 9/8/2004 | 9/9/2004 | 9/9/2004 12:00:00 AM | P | PASS |
|
|
Cell phone ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino
|
FIR04-00440
| INSP-Final Inspection | 9/8/2004 | 9/9/2004 | 9/9/2004 12:00:00 AM | P | PASS |
|
|
Cell PH. ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino
|
FIR04-00055
| INSP-Final Inspection | 9/8/2004 | 9/9/2004 | 9/9/2004 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 9/8/2004 at 11:06:06 AM. Contact: ###-####. Wrong strobes installed in elevator lobbies 9/10/2004 9:25:53 AM
|
FIR04-00419
| INSP-Final Inspection | 9/8/2004 | 9/9/2004 | 9/9/2004 12:00:00 AM | P | PASS |
|
|
###-####-- mark Second and third floors okay - per plans; need to complete FIR04-00055 per agreement 9/10/2004 9:27:15 AM
|
BLD04-00553
| FIRE-Final Inspection | 9/9/2004 | 9/9/2004 | 9/9/2004 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 9/9/2004 at 7:50:45 AM. Contact: ###-####. Card/plans are in new office; sprinklers/alarms were okay without modifications 9/9/2004 2:52:06 PM
|
BLD04-00572
| FIRE-Final Inspection | 9/9/2004 | 9/9/2004 | 9/9/2004 12:00:00 AM | P | PASS |
|
|
jack; Phone #: ###-#### Internet Inspection Request from: Annette Moore GC will have door hardware/closures for structural inspector as they weren't completed 9/9/2004 2:36:36 PM
|
BLD03-02673
| FIRE-Final Inspection | 9/9/2004 | 9/9/2004 | 9/9/2004 12:00:00 AM | P | FAIL |
|
|
john; Phone #: ###-#### Internet Inspection Request from: Annette Moore Front door to be keyed both sides; basement doors need hardware per plans 9/9/2004 3:09:20 PM
|
FIR04-00461
| INSP-Final Inspection | 9/9/2004 | 9/9/2004 | 9/9/2004 12:00:00 AM | P | PASS |
|
|
Installed per plans; the system lacks a smoke detector above the panel; strobes not sync'd and not temporal but are outside the TI area 9/9/2004 12:08:52 PM
|
FIR04-00461
| INSP-Final Inspection | 9/9/2004 | 9/9/2004 | 9/9/2004 12:00:00 AM | P | PASS |
|
|
Installed per plans; the system lacks a smoke detector above the panel; strobes not sync'd and not temporal but are outside the TI area 9/9/2004 12:08:59 PM
|
BLD04-01244
| FIRE-Final Inspection | 9/9/2004 | 9/9/2004 | 9/9/2004 12:00:00 AM | P | PASS |
|
|
|