Inspections for the day of: Thursday, September 9, 2004.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00442 INSP-Final Inspection9/9/20049/9/20049/9/2004 8:28:42 AMPCANC
Troy, Please call as soon as you know your afternoon schedule. We have to schedule with the electrician and building owner. My cell is ###-####. Thanks, Jason; Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
BLD04-01414 FIRE-Sprinkler Rough-in9/8/20049/9/20049/9/2004 12:00:00 AMACANC
shawn; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
FIR04-00498 INSP-Final Inspection9/8/20049/9/20049/9/2004 12:00:00 AMAPASS
suppression system operated correctly. Not all appliances had been installed under the hood yet. I measured them and they will fit under the hood with the required 6" clearance. I will double check at life safety final. 9/9/2004 11:34:04 AM
BLD04-00053 FIRE-Final Inspection9/8/20049/9/20049/9/2004 12:00:00 AMAPASS
Fire life safety finaled 9/9/2004 9:41:00 AM
BLD04-00578 FIRE-Final Inspection9/9/20049/9/20049/9/2004 12:00:00 AMPFAIL
Repair emergency light at the main entry/exit. Provide exit discharge lighting per drawing sheet A-1 and note #30 of the building review notes. Provide updated inspection for the fire extinguishers. Verify fire dept has received tenant space key for placement in the knox key box per review note #19 9/9/2004 4:27:54 PM
FIR04-00505 INSP-Final Inspection9/9/20049/9/20049/9/2004 12:00:00 AMPFAIL
Resubmit plans per review note #8. The addition of the rooftop unit has blocked coverage of the upright sprinkler head. Per the sprinkler head data sheet it appears that three types of sprinkler heads are being used. A 3/8" a 1/2" and a 3/4" are not crossed out on the data sheet. Specify which head is being used and in which location. Provide info and SIN number on the resubmittals. Provide access to the sprinkler heads such as a ladder for verification of specific head type and correct esch. Upright sprinkler heads have less than 1" clearance from ceiling to deflector. See NFPA 13; 8.6.4.1.1.1. Atleast one of the pipe hangers appear to be screwed into partical board above the ceiling. Provide verification this is acceptable and verification the other hangers meet NFPA 13 requirements. Upright heads are spaced 8'-6" off of the exterior wall in the concealed spaced. Provide verification "small room rule" can also be "small cavity rule" or add/relocate uprights. 9/9/2004 3:03:13 PM
FIR04-00407 INSP-Final Inspection9/7/20049/9/20049/9/2004 12:00:00 AMPCANC
Rescheduled for tomorrow morning 9/9/2004 2:50:46 PM