Inspections for the day of: Friday, September 9, 2005.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorWilliam E Thomas
TitleELE-INSPECTOR
Phone #794-9492
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02348 Final9/8/20059/9/20059/9/2005 4:49:29 PMAFAIL
Internet Inspection Request from: Latisha Peltier
1. BCC "No violation shall remain" race way supporting in electrical room and store room.
ELE05-03076 Permanent Service9/8/20059/9/20059/9/2005 3:08:21 PMAFAIL
###-####
stop work issued, no building permits. Electrical permit issued to a trustee.
ELE05-03240 Temporary Service9/8/20059/9/20059/9/2005 1:32:10 PMAFAIL
nicole; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
1. 300.5 shall be protected at least 18" into the ground
2. 406.8 recep shall have weather proof cover.
ELE05-03270 Electrical Rough-In9/8/20059/9/20059/9/2005 12:43:38 PMAPASS
rocky; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
ri ok, no p/s
ELE05-03272 Temporary Service9/8/20059/9/20059/9/2005 10:20:04 AMAPASS
###-#### - nicole
tt/s u/g n ok
ELE05-02988 Electrical Rough-In9/8/20059/9/20059/9/2005 10:09:37 AMAPASS
ground rod inpsection on south unit only please////matt ###-####
ok to cover concrete
ELE05-03239 Rough-In Permanent Service9/9/20059/9/20059/9/2005 9:55:18 AMAPART
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs
ri only ok, no p.s.
needs ufer
ELE05-03288 Rough-In Permanent Service9/9/20059/9/20059/9/2005 9:54:35 AMAPART
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs
ri only no p.s.
needs ufer
ELE05-02988 Permanent Service9/9/20059/9/20059/9/2005 12:00:00 AMAPASS
ground rod inpsection on south unit only please////matt ###-####
p/s u/g n ok