Inspections for the day of: Tuesday, September 9, 2008.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-01020 BLD-Aging Inspection9/9/20089/9/20089/11/2008 10:24:25 AM CANC
FIR08-00164 INSP-Final Inspection9/9/20089/9/20089/10/2008 10:04:39 AMPFAIL
Noted several spacing issues at the SW branch line adjacent to the overhead doors, missing PRV at the riser, trapeeze hanger at the last piece of 6" main is overspaced, FDC piping is missing hanger support and bracing at the vertical run, noted added head at the electrical room, provide riser tags, signage, DCVA certification, and complete forward flow testing in conjunction with riser supervision. Site inspection completed 9/9.
FIR08-00391 FIR-Aging Inspection9/9/20089/9/20089/10/2008 7:42:00 AM DONE
Work in progress, construction underway.
FIR08-00281 INSP-Conference9/8/20089/9/20089/10/2008 7:41:13 AMPDONE
On site visit regarding SW head locations and project scheduling.
FIR08-00474 INSP-Sprinkler Rough-in9/9/20089/9/20089/10/2008 7:37:43 AMPPART
OH rough-in is approved for cover at the TI drop ceilings.
FIR08-00587 INSP-Final Inspection9/8/20089/9/20089/9/2008 2:41:45 PMPPASS
Scope of work completed per plan, fire sprinkler permit finaled.
FIR08-00466 INSP-Final Inspection9/8/20089/9/20089/9/2008 2:40:36 PMPPASS
Upright sprinkler protection is acceptable pending the complete removal of the grid ceiling.
FIR08-00542 INSP-Final Inspection9/8/20089/9/20089/9/2008 2:38:58 PMPFAIL
Upright heads at one branch line do not meet obstruction tables per NFPA 13 8.6.5.1.2 due to adjacent ductwork.
FIR08-00163 INSP-Final Inspection9/9/20089/9/20089/9/2008 11:47:05 AMAFAIL
One upright head adjacent to the mech. room is too close to the wall, FDC piping needs a hanger on the horizontal piece and bracing/support for the vertical run, missing PRV at the riser, noted one added head at the electrical room. Riser needs calc. stickers, signage, backflow certification, forward flow test, and tamper/flow testing in conjunction with the fire alarm work.
BLD08-01879 FIRE-Final Inspection9/8/20089/9/20089/9/2008 10:22:42 AMAFAIL
Need to provide signage and approved hardware at the main entry/exit door per discussion and project review notes.