Inspections for the day of: Wednesday, September 9, 2009.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-01637 Electrical Rough-In9/9/20099/9/20099/9/2009 3:46:43 PMPPASS
ryan - please call 1/2 hr prior Phone #: ###-#### ric ok, no esc this project
ESC09-00281 General Inspection9/9/20099/9/20099/9/2009 3:12:35 PMPPASS
looked ok
ELE09-01472 Final9/9/20099/9/20099/9/2009 2:10:32 PMPCANC
Inspect new panel behind garage port & rough-in in small room in car port (third door from the left). Laundry Circuits. Phone #: ###-#### Internet Inspection Request from: nathan palmer wrong type request, see ri
ELE09-01472 Electrical Rough-In9/9/20099/9/20099/9/2009 2:10:03 PMPPASS
Inspect new panel behind garage port & rough-in in small room in car port (third door from the left). Laundry Circuits. Phone #: ###-#### Internet Inspection Request from: nathan palmer ric ok, no esc this project
ELE09-01688 Electrical Rough-In9/9/20099/9/20099/9/2009 12:53:33 PMPPASS
Scheduled by a contractor via Hello! on 9/9/2009 at 10:02:36 AM. Contact: ###-####. corrections made, ric ok, ok to pour concrete encased electrode
ELE09-01688 Rough-In Permanent Service9/9/20099/9/20099/9/2009 12:52:14 PMPCANC
Scheduled by a contractor via Hello! on 9/9/2009 at 10:02:36 AM. Contact: ###-####. wrong type request, see ri
ESC09-00281 General Inspection9/9/20099/9/20099/9/2009 10:55:18 AMAPASS
looked ok
ELE09-01134 Final9/9/20099/9/20099/9/2009 10:06:12 AMAPASS
Scheduled by a contractor via Hello! on 9/9/2009 at 6:56:54 AM. Contact: ###-####. corrections made, ok to final, can"t add esc response
ELE09-01681 Electrical Rough-In9/8/20099/9/20099/9/2009 10:03:41 AMAFAIL
Anayn ###-#### called, left message, left correction notice, NEC 300.14 shall provide 6" free conductor length at boxes, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 110.12(B) electrical equipment and surfaces shall not be contaminated by foreign material, 250.148(C) shall use ground screws in metal boxes, 210.52(A)(2) shall provide receptacles in 2' walls, 334.30 nm cable shall be secured within 12" of panel and boxes, no esc this project
ELE09-01688 Rough-In Permanent Service9/8/20099/9/20099/9/2009 9:02:04 AMAFAIL
Scheduled by a contractor via Hello! on 9/8/2009 at 3:13:35 PM. Contact: ###-####. called, left correction notice, NEC 300.14 at least 6" free conductor shall be left at each point where it emerges from raceway for splice, 300.4 shall provide steel plate where bored hole is less than 1 1/4" from edge of framing member, 250.52(A)(3) concrete encased electrode shall have 2" concrete encasement, 230, shall provide service clearance for existing building