FIR09-00386
| INSP-Final Inspection | 9/9/2009 | 9/9/2009 | 9/9/2009 4:43:01 PM | P | PART |
|
|
Corrections verified for completion, fire alarm system testing passed, XP strobes at the fuel station area are not installed.
|
FIR09-00317
| INSP-Sprinkler Rough-in/Hydro | 9/9/2009 | 9/9/2009 | 9/9/2009 4:39:00 PM | P | FAIL |
|
|
System #2 failed hydrostatic test. Systems #1,3, and 4 passed hydrostatic tests.
|
FIR09-00310
| FIR-Aging Inspection | 9/9/2009 | 9/9/2009 | 9/9/2009 2:47:52 PM | | DONE |
|
|
Pending site inspection request for permit final.
|
BLD09-00835
| FIRE-Final Inspection | 9/9/2009 | 9/9/2009 | 9/9/2009 2:45:13 PM | P | PASS |
|
|
Second same day visit to verify corrections are finished, testing passed, fire life safety finaled.
|
BLD09-00835
| FIRE-Final Inspection | 9/9/2009 | 9/9/2009 | 9/9/2009 2:43:53 PM | P | FAIL |
|
|
Trouble light indicators at two duct detectors are not clear, contractor not available on site to commence repairs or testing.
|
FIR09-00478
| INSP-Sprinkler Rough-in/Hydro | 9/9/2009 | 9/9/2009 | 9/9/2009 2:40:31 PM | P | PART |
|
|
See annotations on approved plans for overhead work at the 2nd and 3rd floor drop and sheetrock ceilings okayed for cover.
|
BLD09-01209
| FIRE-Final Inspection | 9/9/2009 | 9/9/2009 | 9/9/2009 2:38:42 PM | P | FAIL |
|
|
Pending rack permit as previously noted.
|
FIR09-00522
| INSP-Sprinkler Rough-in | 9/9/2009 | 9/9/2009 | 9/9/2009 2:37:47 PM | P | PART |
|
|
Overhead fire sprinkler modifications at the remodel area are approved for cover.
|
BLD09-00168
| FIRE-Final Inspection | 9/8/2009 | 9/9/2009 | 9/9/2009 2:36:32 PM | A | NR |
|
|
Project related fire alarm permit work must pass inspection for final status prior to building fire life safety approval.
|
FIR09-00434
| INSP-Final Inspection | 9/8/2009 | 9/9/2009 | 9/9/2009 11:16:08 AM | A | PASS |
|
|
Fire alarm testing passed, permit finaled.
|
BLD06-01199
| FIRE-Final Inspection | 9/9/2009 | 9/9/2009 | 9/9/2009 11:14:22 AM | P | PASS |
|
|
C/N items finished, note-manual thumbturn at the main entry/exit office door has been disabled.
|