Inspections for the day of: Wednesday, September 9, 2009.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00386 INSP-Final Inspection9/9/20099/9/20099/9/2009 4:43:01 PMPPART
Corrections verified for completion, fire alarm system testing passed, XP strobes at the fuel station area are not installed.
FIR09-00317 INSP-Sprinkler Rough-in/Hydro9/9/20099/9/20099/9/2009 4:39:00 PMPFAIL
System #2 failed hydrostatic test. Systems #1,3, and 4 passed hydrostatic tests.
FIR09-00310 FIR-Aging Inspection9/9/20099/9/20099/9/2009 2:47:52 PM DONE
Pending site inspection request for permit final.
BLD09-00835 FIRE-Final Inspection9/9/20099/9/20099/9/2009 2:45:13 PMPPASS
Second same day visit to verify corrections are finished, testing passed, fire life safety finaled.
BLD09-00835 FIRE-Final Inspection9/9/20099/9/20099/9/2009 2:43:53 PMPFAIL
Trouble light indicators at two duct detectors are not clear, contractor not available on site to commence repairs or testing.
FIR09-00478 INSP-Sprinkler Rough-in/Hydro9/9/20099/9/20099/9/2009 2:40:31 PMPPART
See annotations on approved plans for overhead work at the 2nd and 3rd floor drop and sheetrock ceilings okayed for cover.
BLD09-01209 FIRE-Final Inspection9/9/20099/9/20099/9/2009 2:38:42 PMPFAIL
Pending rack permit as previously noted.
FIR09-00522 INSP-Sprinkler Rough-in9/9/20099/9/20099/9/2009 2:37:47 PMPPART
Overhead fire sprinkler modifications at the remodel area are approved for cover.
BLD09-00168 FIRE-Final Inspection9/8/20099/9/20099/9/2009 2:36:32 PMANR
Project related fire alarm permit work must pass inspection for final status prior to building fire life safety approval.
FIR09-00434 INSP-Final Inspection9/8/20099/9/20099/9/2009 11:16:08 AMAPASS
Fire alarm testing passed, permit finaled.
BLD06-01199 FIRE-Final Inspection9/9/20099/9/20099/9/2009 11:14:22 AMPPASS
C/N items finished, note-manual thumbturn at the main entry/exit office door has been disabled.