Inspections for the day of: Thursday, September 9, 2010.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD10-00458 FIRE-Final Inspection9/9/20109/9/20109/9/2010 2:46:07 PMPFAIL
Mount the fire extinguisher as discussed.
FIR10-00336 INSP-Final Inspection9/9/20109/9/20109/9/2010 1:12:07 PMPPASS
Permit finaled
BLD10-00973 FIRE-Final Inspection9/8/20109/9/20109/9/2010 11:45:08 AMAFAIL
The three exit signs did not operate on emergency power. Per the plan reviewer the emergency lighting shown on the plans is not required to be installed.
BLD06-02048 FIRE-Final Inspection9/8/20109/9/20109/9/2010 11:43:50 AMAPASS
Life safety passed.
FIR10-00393 INSP-Final Inspection9/8/20109/9/20109/9/2010 11:43:08 AMAPASS
Permit finaled
BLD10-01718 FIRE-Final Inspection9/8/20109/9/20109/9/2010 11:37:56 AMAFAIL
No access to the inside of the storage shed which is where the drawings were located and the contractor was in cascade.
FIR10-00426 INSP-Final Inspection9/9/20109/9/20109/9/2010 11:06:20 AMPPASS
Permit finaled. The netcon was 5
FIR10-00402 INSP-Final Inspection9/8/20109/9/20109/9/2010 10:26:49 AMAFAIL
Still need to test the duct smoke detectors, heat detectors and smoke detectors. A single smoke detector needs to be provided on the south side of the beam and the two smoke detectors in the center of the dining area need to be mounted at the roof deck instead of the bottom chord of the trusses. One strobe needed to have the candella increased due to overspacing. The PIV tamper switch was wired backwards and one other tamper switch had been by-passed. Both were repaired while I waited. The EOL tested ok as well as the sprinkler system devices and the hood suppression system. Signal reports are needed showing todays work.
FIR10-00342 INSP-Final Inspection9/8/20109/9/20109/9/2010 10:12:58 AMAPASS
permit finaled
FIR10-00389 INSP-Final Inspection9/8/20109/9/20109/9/2010 9:23:55 AMAPASS
The hood suppression system operated correctly.